|
CHAPTER 13-196 -
EXISTING BUILDINGS MINIMUM REQUIREMENTS
13-196-010
Application.
13-196-020
Occupancy.
13-196-030
Structural stability.
13-196-031
Maintenance of exterior walls and enclosures
Definitions.
13-196-032
Maintenance of exterior walls and enclosures
Application.
13-196-033
Maintenance of exterior walls and enclosures
Maintenance and reporting required.
13-196-034
Maintenance of exterior walls and enclosures Critical
examination program.
13-196-035
Ongoing inspection and repair program.
13-196-036
Maintenance of exterior walls and enclosures Unsafe
exterior walls and enclosures.
13-196-036.5
Maintenance of exterior walls and enclosures Reports to
the commissioner.
13-196-037
Ongoing inspection and repair program.
13-196-038
Fines and penalties.
13-196-038.5
Rules and regulations.
13-196-040
Floor loading.
13-196-050
Exit requirements.
13-196-060
Exits Generally.
13-196-070
Exits Types.
13-196-080
Passageways and exits to be unobstructed.
13-196-084
Stairwell re-entry in existing buildings.
13-196-085
Stairwell identification.
13-196-086
Area of rescue assistance identification.
13-196-090
Exit, stairway, fire escape and directional signs.
13-196-100
Smoke detectors Where required.
13-196-110
Smoke detectors Installation near sleeping rooms and in
living levels.
13-196-120
Smoke detectors Interior stairwell installation.
13-196-130
Smoke detectors Standards.
13-196-140
Smoke detectors Owner/tenant responsibilities.
13-196-150
Smoke detectors Unlawful acts.
13-196-160
Smoke detectors Multifamily and single-family
installation When.
13-196-165
Carbon monoxide detectors.
13-196-170
Self-closing devices required for corridor doors.
13-196-180
Sprinkler systems Where required.
13-196-190
Standpipe systems Where required.
13-196-200
Standard fire alarm system requirements.
13-196-203
Life safety data sheet Required.
13-196-204
Voice communication systems in existing buildings.
13-196-205
Automatic sprinkler system installation in existing
high-rise buildings.
13-196-206
Life safety evaluation of existing high-rise buildings.
13-196-207
Materials and installation standards for retrofit fire
protection systems.
13-196-208
Smokeproof towers in existing high- rise buildings Fire
shields.
13-196-209
High-rise buildings Stairways Doors Frames.
13-196-210
High rise fire systems.
13-196-220
Class II standard fire alarm systems.
13-196-230
Floor area and height.
13-196-240
Automatic fire detectors Where required.
13-196-250
Permitted omission of sprinklers, heat and smoke
detectors.
13-196-260
Fire extinguishers.
13-196-270
Elevator recall.
13-196-280
Reserved.
13-196-290
Pre-ordinance hotels.
13-196-300
Institutional units.
13-196-310
Roominghouses.
13-196-320
Roominghouses Sanitary facilities.
13-196-330
Roominghouses Responsibility of operator.
13-196-340
Minimum requirements for residential buildings General.
13-196-350
Residential buildings Water closet.
13-196-360
Residential buildings Lavatory.
13-196-370
Residential buildings Bathtub or shower.
13-196-380
Residential buildings Limitations on sharing sanitary
facilities.
13-196-390
Residential buildings Kitchen sink.
13-196-400
Residential buildings Heating facilities.
13-196-410
Residential buildings Heat to be furnished.
13-196-420
Residential buildings Cold and hot water lines.
13-196-430
Residential buildings Hot water to be furnished.
13-196-440
Gas-fired appliances.
13-196-450
Residential buildings Hall and stairway lighting.
13-196-460
Residential buildings Storage beneath stairways.
13-196-470
Residential buildings Space, use and location
Applicability of provisions.
13-196-480
Residential buildings Space requirements.
13-196-490
Residential buildings Space requirements Sleeping
rooms.
13-196-500
Residential buildings Access to water closets.
13-196-510
Residential buildings Ceiling heights.
13-196-520
Residential buildings Basement units.
13-196-530
Residential buildings Foundations, exterior walls and
roofs Maintenance.
13-196-540
Residential buildings Floors, interior walls and
ceilings Maintenance.
13-196-550
Residential buildings Windows, doors and hatchways
Maintenance.
13-196-560
Residential buildings Screens.
13-196-570
Residential buildings Stairways and porches
Maintenance.
13-196-580
Residential buildings Basements and cellars
Maintenance.
13-196-590
Residential buildings Facilities, equipment, chimneys
Maintenance.
13-196-600
Residential buildings Lot grading and drainage.
13-196-610
Residential buildings Responsibilities of owners and
occupants General.
13-196-620
Residential buildings Responsibilities of occupants.
13-196-630
Residential buildings Responsibilities of owner or
operator.
13-196-640
Residential buildings Liability to city.
13-196-641
Application of certain sections.
13-196-650
Pre-ordinance conversion to existing buildings
Applicability.
13-196-660
Conversion of pre-ordinance buildings Height limits.
13-196-670
Stairwells.
13-196-680
Corridors.
13-196-690
Dwelling separations.
13-196-700
Partitions.
13-196-710
Basement ceiling construction.
13-196-720
Heating plants.
13-196-730
Light and ventilation.
13-196-740
One additional dwelling unit over original allowed
Conditions.
13-196-750
Heat required.
13-196-760
Endangering health of employees.
13-196-010 Application.
Every existing
building shall comply with the code requirements in force
and applicable to such building, at the time of its
construction or alteration, and shall also comply with such
provisions of this chapter which are specifically made
applicable to all existing buildings. However, nothing in
this chapter shall be interpreted to prevent the application
of the Chicago Zoning Ordinance, Title 17 of this Code.
(Prior code § 78-1)
13-196-020 Occupancy.
No person shall
occupy as an owner-occupant, or shall let or hold out to
another for occupancy, any building which does not comply
with the requirements of this chapter.
(Prior code § 78-2)
13-196-030 Structural stability.
If there is any
doubt as to the structural stability of any building or
structure, or parts thereof, the building commissioner may
request such building or structure, or parts thereof, to be
critically examined by a licensed architect or registered
structural engineer employed by such owner, agent or person
in charge, possession or control of any such building,
structure, or part thereof.
Said licensed
architect or registered structural engineer shall render a
report in writing, showing the structural condition of the
building, structure or part thereof. Two copies of the
report shall in turn be submitted to the building
commissioner. One copy of said report shall, if
satisfactory, be retained by the building commissioner, and
one be returned to the owner, agent or person in charge,
possession or control of said building, structure or parts
thereof, bearing a stamp of approval signed by said building
commissioner.
(Prior code § 78-3;
Amend Coun. J. 9-13-89, p. 4604)
13-196-031 Maintenance of exterior walls
and enclosures Definitions.
These terms shall
have the following meanings when used in Sections 13-196-031
through 13-196-036, which sections shall be known as the
minimum requirements for maintenance of exterior walls and
enclosures, as further clarified by such rules and
regulations promulgated by the commissioner of buildings
pursuant to Section 13-196-037:
Critical
examination shall mean a close-up visual examination of the
condition of all elevations of the exterior walls and
enclosure. For buildings constructed of material other than
terra cotta, the examination may be satisfied by scaffolding
utilizing alternate drops to cover at least 50 percent of
the area of each elevation, and including all corners of the
building. For buildings constructed of terra cotta material,
the examination shall cover the entire area of all
elevations. All examinations shall be performed by or under
the direct supervision of a professional employed by the
owner/agent for the purpose of determining if remedial work
is required.
Ongoing
inspection and repair shall mean a program of bi-annual
inspections by a professional retained by the owner/agent,
with accompanying report by the professional to the
commissioner of buildings and repair work by the owner/agent
as necessary.
Ornamental
Piece shall mean any terra cotta, stone or other decorative
addition to a building defined in Section 13-196-032 that is
primarily secured to the substrate by a metal fastener.*
Owner/agent
shall mean the owner, agent or person in charge, possession
or control of the building.
Professional
shall mean an Illinois licensed architect or Illinois
licensed structural engineer.
(Added Coun. J.
7-31-02, p. 91358, § 1; Amend Coun. J. 9-4-02, p. 92710, §
1)
13-196-032 Maintenance of exterior walls
and enclosures Application.
Exterior walls
and enclosures and parts thereof of buildings that are 80
feet or more in height above grade, shall comply with
Sections 13-196-033 to 13-196-036.
(Added Coun. J.
7-31-02, p. 91358, § 1; Amend Coun. J. 9-4-02, p. 92714, §
1)
13-196-033 Maintenance of exterior walls
and enclosures Maintenance and reporting required.*
It shall be the
owner/agents duty to maintain the buildings exterior walls
and enclosures in a safe condition and to provide periodic
reports to the commissioner of buildings. In furtherance of
that requirement:
(a) the
owner/agent shall: 1) arrange for periodic critical
examinations at four year intervals or at longer intervals
otherwise designated in rules and regulations promulgated by
the commissioner of buildings pursuant to 13-196-038.5 and
2) establish an ongoing inspection and repair program at two
year intervals for each of the intervening years.
(b) The
owner/agent of buildings constructed substantially of brick,
shall: (1) arrange for periodic critical examinations at
four year intervals, or at longer intervals otherwise
established by the commissioner, of the ornamental pieces
and the parapet wall; (2) arrange for critical examinations
at four year intervals or at longer intervals otherwise
established by the commissioner, of the lentils, which may
be satisfied by scaffolding utilizing one drop per
elevation; and (3) establish an ongoing inspection and
repair program at two year intervals for the remainder of
the exterior walls and enclosures of the building during the
intervening years.
When the report
indicates that repair or remedial work is necessary, the
report shall include a proposed schedule for completion of
such work.
(Added Coun. J.
7-31-02, p. 91358, § 1; Amend Coun. J. 9-4-02, p. 92710, §
1)
13-196-034 Maintenance of exterior walls
and enclosures Critical examination program.*
(a) The
initial critical examination shall be submitted for all
buildings constructed prior to January 1, 1950, by December
1, 2003, and on all buildings constructed on or after
January 1, 1950, by December 1, 2004. The initial critical
examination for newly constructed buildings shall be
submitted no later than December 1 of the fourth year
following completion of the construction.
(b) Following
the initial critical examination, the exterior walls and
enclosures and parts thereof on all buildings shall be
subsequently critically examined and a report submitted at
least once every four years no later than November 1 of the
fourth year following the previous examination unless
otherwise designated in rules and regulations promulgated by
the commissioner of buildings pursuant to Section
13-196-038.5 of this code. Any building which cannot be
categorized according to the information contained in a
previously submitted critical examination report shall be
required to supplement such report with a certification by a
professional as to which category the building belongs.
(c) The
critical examination shall include a review of all previous
reports.
(d) The
professional shall prepare a report in writing on the
critical examination, describing the condition of the
exterior walls and enclosures on the building and including
a record of the components and cladding including, without
limitation, any broken glass and loose or missing glazing
components; loose masonry, concrete, EIFS, metal, stone or
terra cotta; and all significant deterioration and
displacement observed. Additionally, the report shall
indicate any imminently dangerous conditions. If any
remedial work is recommended the report shall indicate the
nature and urgency of such work.
(Added Coun. J.
7-31-02, p. 91358, § 1; Amend Coun. J. 9-4-02, p. 92710, §
1)
13-196-035 Ongoing inspection and repair
program.*
(a) The
ongoing inspection and repair program shall provide
inspection, reporting and preventive maintenance of the
exterior walls and enclosures and parts thereof.
(b) No later
than November 1 of every other calendar year, the
professional employed by the owner/agent shall prepare a
report in writing on the ongoing inspection and repair
program, describing the condition of the exterior walls and
enclosures and parts thereof on the building and on any
inspections, surveys or repair work performed or to be
performed on the exterior walls and enclosures.
(Amend Coun. J.
7-31-02, p. 91358, § 1)
13-196-036 Maintenance of exterior walls
and enclosures Unsafe exterior walls and enclosures.
Every exterior
wall and enclosure and parts thereof found to be in an
unsafe condition shall be subject to notice by the
commissioner of buildings to the owner/agent to take
appropriate precautionary measures and effect such repairs
or reinforcements in a timely manner as will bring the
building exterior walls and enclosures and parts thereof
into a safe condition. The owner/agent of any building which
constitutes an imminent danger and hazard to the public
shall take immediate action to have a critical examination
performed upon such building and provide the ensuing report
to the department of buildings. Additionally, the
owner/agent shall promptly begin and complete the removal,
reinforcement and/or permanent repairs necessary to make the
premises conform to the building provisions of this code,
and provide structurally safe conditions. Any costs incurred
by any department of the city in taking emergency actions
due to the dangerous and hazardous condition of an unsafe
exterior wall, including, but not limited to: closure of
vehicular traffic in a public street, rerouting of
pedestrian traffic on a public sidewalk; erection or
installation of partitions, canopies, sidewalk sheds,
barricades, scaffolding or netting, shall be a debt due and
owing to the city and recoverable from the owner/agent of
such building.
(Added Coun. J.
7-31-02, p. 91358, § 1)
13-196-036.5 Maintenance of exterior walls
and enclosures Reports to the commissioner.
The owner/agent
shall submit to the commissioner of buildings two copies of
the report required under Section 12-196-034 or 12-196-035.
The report shall bear the professionals seal and signature.
If acceptable, one copy of the report shall be returned to
the owner/agent, bearing a stamp indicating acceptance by
the commissioner of buildings. The owner/agent shall
maintain such reports in a permanent building file for
future reference. The fee for examination of reports shall
be $10.00 per report. However, reports requiring extensive
review of technical information by licensed professionals
within the department of buildings shall be examined for a
fee of $200.00. All reports shall identify any persons or
entities involved in the preparation of completion of the
examination and report under both the critical examination
program and the ongoing inspection and repair program. All
reports shall also include as exhibits or attachments any
and all documents, notes, summaries, memoranda, letters or
ancillary reports submitted by the professional to the owner
of buildings subject to these requirements
(Added Coun. J.
1-1-96, p. 14639; Amend. 8-30-00, p. 39656)
13-196-038 Fines and penalties.
Any violation of
or interference with the enforcement of any provision of
Section 13-196-031 through and including Section 13-196-037,
and of Sections 13-196-204 through and including 13-196-209,
shall be punishable by a fine of not less than $500.00 and
not more than $1,000.00 for each offense. Each day that a
violation continues shall constitute a separate and distinct
offense for which a fine as herein provided shall be
imposed.
(Added Coun. J.
7-31-02, p. 91358, § 1; Amend Coun. J. 12-15-04, p. 39962, §
10)
13-196-032
Maintenance of exterior walls and enclosures Application.
Exterior walls and enclosures and parts thereof of
buildings that are 80 feet or more in height above grade,
shall comply with Sections 13-196-033 to 13-196-036.
13-196-033
Maintenance of exterior walls and enclosures Maintenance
and reporting required.
It shall be the owner / agents duty to maintain the
buildings exterior walls and enclosures in a safe condition
and to provide periodic reports to the commissioner of
buildings. In furtherance of that requirement:
(a) The owner / agent shall: (1) arrange for periodic
critical examinations at four year intervals or at longer
intervals otherwise established by the commissioner and (2)
establish an ongoing inspection and repair program at two
year intervals during the intervening years.
(b) The owner / agent of buildings constructed
substantially of brick, shall: (1) arrange for periodic
critical examinations at four year intervals, or at longer
intervals otherwise established by the commissioner, of the
ornamental pieces and the parapet wall; (2) arrange for
critical examinations at four year intervals, or at longer
intervals otherwise established by the commissioner, of the
lentils, which may be satisfied by scaffolding utilizing one
drop per elevation; and (3) establish an ongoing inspection
and repair program at two year intervals for the remainder
of the exterior walls and enclosures of the building during
the intervening years.
When the report indicates that repair or remedial work is
necessary, the report shall include a proposed schedule for
completion of such work.
13-196-034
Maintenance of exterior walls and enclosures Critical
examination program.
(a) The initial critical examination shall be
submitted for all buildings constructed prior to January 1,
1950, by November 1, 2003, and on all buildings constructed
on or after January 1, 1950 by December 31, 2004.
(b) Following the initial critical examination, the
exterior walls and enclosures and parts thereof on all
buildings shall be subsequently critically examined and a
report submitted at least once every four years no later
than November 1 of the fourth year following the previous
examination unless otherwise extended by the commissioner of
buildings pursuant to Section 13-196-033 of this code.
(c) The critical examination shall include a review
of all previous reports.
(d) The professional shall prepare a report in
writing on the critical examination, describing the
condition of the exterior walls and enclosures on the
building and including a record of the components and
cladding including, without limitation, any broken glass and
loose or missing glazing components; loose masonry,
concrete, EIFS, metal, stone or terra cotta; and all
significant deterioration and displacement observed.
Additionally, the report shall indicate any imminently
dangerous conditions. If any remedial work is recommended
the report shall indicate the nature and urgency of such
work.
13-196-035
Maintenance and reporting required.
It shall be the owner / agents duty to maintain the
buildings exterior walls and enclosures in a safe condition
and provide periodic reports to the commissioner of
buildings. In furtherance of that requirement, the owner /
agent shall: 1) arrange for periodic critical examinations
at four intervals and 2) establish an ongoing inspection and
repair program at two year intervals for each of the
intervening years. When the report indicates that repair or
remedial work is necessary, the report shall include a
proposed schedule for completion of such work. Provided,
however, that the due date for the next critical examination
may be extended by the commissioner of buildings for a
period not longer than three years based upon the extent and
durability of such repairs.
13-196-036
Maintenance of exterior walls and enclosures Unsafe
exterior walls and enclosures.
(a) Every exterior wall and enclosure and parts
thereof found to be in a unsafe condition shall be subject
to notice by the commissioner of buildings to the owner /
agent to take appropriate precautionary measures and effect
such repairs or reinforcements in a timely manner as will
bring the building exterior walls and enclosures and parts
thereof into a safe condition. The owner / agent of any
building which constitutes an imminent danger and hazard to
the public shall take immediate action to have a critical
examination performed upon such building and provide the
ensuing report to the department of buildings. Additionally,
the owner / agent shall promptly begin and complete the
removal, reinforcement and / or permanent repairs necessary
to make the premises conform to the building provisions of
this code, and provide structurally safe conditions. Any
costs incurred by any department of the city in taking
emergency actions due to the dangerous and hazardous
condition of an unsafe exterior wall, including, but not
limited to: closure of vehicular traffic in a public street,
rerouting of pedestrian traffic on a public sidewalk;
erection or installation of partitions, canopies, sidewalk
sheds, barricades, scaffolding or netting, shall be a debt
due and owing to the city and recoverable from the owner /
agent of such building.
13-196-037
Ongoing inspection and repair program.
(a) The ongoing inspection and repair program shall
provide inspection, reporting and preventive maintenance of
the exterior walls and enclosures and parts thereof.
(b) No later than November 1 of every other calendar
year, the professional employed by owner / agent shall
prepare a report in writing of the ongoing inspection and
repair program, describing the condition of the exterior
walls and enclosures and parts thereof on the building and
on any inspections, surveys or repair work performed or to
be performed on the exterior walls and enclosures.
13-196-038 Fines
and penalties
Any violation of or interference with the enforcement of
any provisions of Section 13-196-031 through and including
Section 13-196-037 shall be punishable by fine of not less
than $500.00 and not more than $1,000.00. Each day that such
violation shall continue shall constitute a separate and
distinct offense for which a fine as herein provided shall
be imposed.
13-196-038.5 Rules and regulations.
The commissioner
of buildings may issue rules and regulations for the
administration and enforcement of the minimum requirements
for maintenance of exterior walls and enclosures. Any person
violating such rules and regulations shall be subject to the
fines prescribed in Section 12-196-039.
(Added Coun. J.
8-30-00, p. 39656)
13-196-040 Floor loading.
Every existing
building shall be so constructed and maintained as to
support safely the loads prescribed in Chapter 13-52 of this
Code, except that in building of mercantile, industrial or
storage occupancies the department of construction and
permits and fire commissioner may permit occupancy of
buildings having lower load-bearing capacity, when satisfied
that such capacity will not be exceeded by the specific
occupant. Such approved floor loads shall be posted as
required in Section 13-52-190.
In buildings
where the safe load-bearing capacity is in doubt, owing to
deterioration of materials or other reasons, the building
commissioner and fire commissioner shall require load tests
to determine the safe bearing capacity. Such load tests
shall comply with the requirements of Section 13-120-110.
(Prior code § 78-4;
Amend Coun. J. 9-13-89, p. 4604; Amend Coun. J. 6-14-95, p.
2841; Amend Coun. J. 3-5-03, p. 104990, § 39)
13-196-050 Exit requirements.
Existing
buildings shall comply with all applicable exit requirements
of this Code and with the special provisions of Sections
13-196-060 to 13-196-090, inclusive.
(Prior code § 78-5)
13-196-060 Exits Generally.
In existing
buildings where exits do not comply with the requirements of
Chapter 13-160 and in which hazardous conditions exist
because of the number, width, construction or location of
exits, the building commissioner and fire commissioner may
order additional exits to assure adequate safety of the
occupants. Every existing building shall have not less than
the minimum number of required exits, as prescribed in
Section 13-160-050.
(Prior code § 78-6;
Amend Coun. J. 9-13-89, p. 4604)
13-196-070 Exits Types.
In pre-ordinance
buildings (built before July 7, 1957), the building
commissioner and fire commissioner may approve the following
types of exits in lieu of the required means of vertical
exit prescribed in Section 13-160-030.
(a) Fire
escape stairways complying with the requirements of Section
13-160-630 may be used in lieu of not more than 50 percent
of required stairs.
(b) A
balcony, having an area of not less than 18 square feet and
provided with a ladder of noncombustible materials extending
to the ground, may be used in lieu of one of two required
stairways for a dwelling unit having a floor level not more
than 15 feet above grade.
(Prior code § 78-7;
Amend Coun. J. 9-13-89, p. 4604)
13-196-080 Passageways and exits to be
unobstructed.
Every hallway,
corridor, stairway, exit, fire escape door, and other means
of egress, shall be kept clear and unencumbered at all
times; and every exit area shall be adequately lighted by
electricity, in accordance with Sections 13-160-660 and
13-160-670 of this Code.
(Prior code § 78-8)
13-196-084 Stairwell re-entry in existing
buildings.
(a) In
buildings not required to comply with Chapter 13-76, every
stairwell enclosure that serves more than four stories shall
comply with one of the following requirements, as a minimum
standard:
Option 1.
The stairwell enclosure doors shall not be locked from the
stairwell side at any time, in order to provide re-entry
from the stair enclosure to the interior of the building; or
Option 2.
The stairwell enclosure doors shall be equipped with a
fail-safe electronic lock release system that is activated
both manually, by a single switch accessible to building
management and firefighting personnel, and automatically,
either by approved smoke detectors or sprinkler waterflow
devices, connected to an annunciator panel. If this option
is selected, a telephone or other two-way communications
system connected to an approved station shall be provided at
not less than every fifth floor in each stairway where the
doors to the stairway are locked, no later than January 1,
2005.
During the time
necessary to install a lock release system under this Option
2, but in no event beyond December 31, 2004, the
transitional measures listed as (A) through (E) below may be
used. Doors on stair enclosures may be equipped with
hardware that prevents re-entry into the interior of the
building, provided that all of the following criteria are
met:
(A)
there shall be not less than two levels where doors leading
to the building interior are permanently unlocked,
permitting access to another exit stair; and
(B)
there shall be not more than four stories intervening
between stairwell enclosure doors that provide access to
another exit stair; and
(C)
re-entry to the building interior shall be possible at all
times on the highest story or the second highest story,
whichever allows access to another exit stair; and
(D)
doors allowing re-entry shall be identified as such on the
stair side of the door; and
(E)
doors not allowing re-entry shall be provided with a sign
on the stair side indicating the location of the nearest
door, in each direction of travel, that allows re-entry or
exit.
(b)
Regardless of which option is selected under subsection (a)
of this section, stairwell enclosure doors at the main
egress level of the building shall remain unlocked from the
stairwell enclosure side at all times.
(c) Every
building of more than four stories, and having a height in
excess of 80 feet above grade, shall comply with subsection
(a) of this section upon this sections taking effect. Every
building of more than four stories, and having a height not
exceeding 80 feet above grade, shall comply with subsection
(a) of this section no later than January 1, 2005.
(d) No later
than May 1, 2004, the executive director of the department
of construction and permits and the fire commissioner shall
issue guidelines for the approval of stations in buildings
where Option 2 described in subsection (a) has been
selected.
(e) Nothing
in this section applies to any stairwell enclosure door
which opens directly into a dwelling unit, provided the
dwelling unit door has a self-closer, a latch, and no
self-locking hardware. Where all doors in the stairwell meet
these criteria, the stairwell shall be provided with either
a two-way communication system as required by Option 2
above, or the stairwell shall be provided with readily
operable windows that are operable according to ANSI
A117.1-1998, Section 309 Operable Parts, on each landing or
intermediate landing, no later than January 1, 2005.
(Added Coun. J.
11-19-03, p. 14365, § 1; Amend Coun. J. 12-17-03, p.
15806, § 1)
13-196-085 Stairwell identification.
Within every
building which exceeds three stories in height there shall
be posted and maintained, within every interior stairwell
enclosure at every floor, adjacent to the stairwell door,
alphabetical or directional letter identification for the
stairwell and the number of the floor to which the door
opens. Lettering shall be permanent, a minimum of six inches
in height and comply with A.D.A.A.G. (Americans with
Disabilities Act Accessibility Guidelines) 4.30.1 General,
4.30.4 Raised and Braille Characters and Pictorial Symbol
Signs, 4.30.5 Finish and Contrast, and 4.30.6 Mounting
Location and Height.
Adjacent to every
stairwell door there shall be posted, on the occupancy side,
information showing which floors have re-entry locations.
Lettering shall be permanent and comply with A.D.A.A.G.
4.30.1 General, 4.30.4 Raised and Braille Characters and
Pictorial Symbol Signs, 4.30.5 Finish and Contrast, and
4.30.6 Mounting Location and Height.
(Added Coun. J.
10-31-01, p. 71183, § 3; Amend Coun. J. 5-1-02, p. 84027, §
2)
13-196-086 Area of rescue assistance
identification.
Each area of
rescue assistance shall be identified by a sign which
states area of rescue assistance and displays the
international symbol of accessibility. Lettering shall be
permanent and comply with A.D.A.A.G. 4.30 (Americans with
Disabilities Act Accessibility Guidelines).
(Added Coun. J.
10-31-01, p. 71183, § 3; Amend Coun. J. 5-1-02, p. 84027, §
1)
13-196-090 Exit, stairway, fire escape and
directional signs.
Exit, stairway,
fire escape and directional signs shall be properly
installed and maintained, in accordance with Sections
13-160-700 to 13-160-750 of this Code.
(Prior code § 78-9)
13-196-100 Smoke detectors Where
required.
All existing
dwelling units as defined in Sections 13-56-020 through
13-56-040, inclusive shall be equipped with approved smoke
detectors in accordance with the provisions of Chapter
13-196, Sections 13-196-110 through and including
13-196-160.
(Prior code § 78-10;
Amend Coun. J. 4-15-84, p. 6189; Amend Coun. J. 6-14-95, p.
2841)
13-196-110 Smoke detectors Installation
near sleeping rooms and in living levels.
Every owner,
manager or agent of any building, as described in Section
13-196-100, shall install, in every dwelling unit, not less
than one approved smoke detector on the uppermost ceiling,
not less than four inches from any wall, or on a wall,
located from 12 inches from the ceiling, and within 15 feet
of all rooms used for sleeping purposes, with not less than
one detector per living level containing a habitable room or
unenclosed heating plant.
(Prior code § 78-11;
Amend Coun. J. 4-25-84, p. 6189; Amend Coun. J. 9-8-86, p.
33588)
13-196-120 Smoke detectors Interior
stairwell installation.
Every owner,
manager or agent of any building of Type II, III or IV
construction as described in Section 13-196-100, shall
install not less than one approved smoke detector on the
uppermost ceiling, not less than four inches from any wall,
or on a wall, located from four to 12 inches from the
uppermost ceiling of all interior stairwells.
(Prior code § 78-12;
Amend Coun. J. 9-8-86, p. 33588)
13-196-130 Smoke detectors Standards.
All approved
single station smoke detectors required in this chapter
shall be the ionization or photoelectric type, either
battery powered or 110 volt AC and shall comply with Title
14 of the municipal code of Chicago. Smoke detectors shall
bear the label of a nationally recognized standards testing
laboratory that indicates that the smoke detectors have been
tested and listed as single or single and multiple station
smoke detectors.
In buildings
required to have a standard fire alarm system as specified
in Chapter 13-196 and hotel buildings of Type II, III or IV
construction complying with Section 13-196-210 smoke
detectors in dwelling units shall be of the type tested and
listed for fire protection signaling systems and shall have
an integral audible device.
(Prior code § 78-13;
Amend Coun. J. 4-25-84, p. 6189; Amend Coun. J. 9-8-86, p.
33588)
13-196-140 Smoke detectors Owner/tenant
responsibilities.
The owner shall
be responsible for testing and maintaining detectors in
common stairwells. It shall be the responsibility of the
tenant to provide and maintain functional batteries for each
detector; test and maintain detectors within dwelling units
and to notify the owner or authorized agent in writing of
any deficiencies. The owner shall be responsible for
providing each tenant with written information regarding
detector testing and maintenance.
(Prior code § 78-14;
Amend Coun. J. 4-25-84, p. 6189)
13-196-150 Smoke detectors Unlawful
acts.
It shall be
unlawful for any person to remove batteries or in any way
make inoperable smoke detectors as provided for in this
chapter.
(Prior code § 78-15)
13-196-160 Smoke detectors Multifamily
and single-family installation When.
Smoke detectors
required by this law shall be installed within three months
in all multiple dwellings as defined in Section 13-56-040.
Smoke detectors required in single-family dwellings as
defined in Section 13-56-030 shall be installed within six
months from the date of passage of this ordinance.
(Prior code § 78-15.1;
Added Coun. J. 4-25-84, p. 6189; Amend Coun. J. 6-14-95, p.
2841)
13-196-165 Carbon monoxide detectors.
All existing
buildings shall comply with all applicable requirements in
Chapters 13-64 and 18-28 of this Code for the installation
and maintenance of carbon monoxide detectors.
(Added Coun. J.
3-14-07, p. 99609, § 2)
13-196-170 Self-closing devices required
for corridor doors.
In residential
buildings exceeding four stories in height, all apartment
doors opening upon public corridors shall be equipped with
approved self-closing devices. In all new and existing
single-room occupancy buildings, irrespective of height, all
dwelling unit doors opening to public corridors shall be
equipped with approved self-closing devices.
(Prior code § 78-16;
Amend Coun. J. 5-4-94, p. 49750)
13-196-180 Sprinkler systems Where
required.
The following
existing buildings or structures, or parts thereof, are to
be equipped with sprinkler systems complying with the
requirements of Chapter 15-16:
(a) Every
building of construction Type III or IV and of two stories
or more in height, used in part or in whole as a Type I
school, hospital, infirmary, nursery, orphanage,
sheltered-care home, sanitoria or home for the aged or used
in whole as a Type II school;
(b) Every
building used in whole or in part as a mens cubicle hotel
which does not comply with Section 13-64-020(a) of this
Code;
(c) Every
building used primarily as an exhibition area or in that
portion of any building used as an exhibition area;
(d) Every
building used in whole or in part as a nursing home, as
defined, in Chapter 4-96 of this Code;
(e) Areas
used for storage of combustible containers in new and
existing buildings, with exhibition areas, shall be enclosed
with a two-hour fire resistive construction, and shall be
equipped with a standard sprinkler system, as defined in
Chapter 15-16 of this Code.
(Prior code § 78-17)
13-196-190 Standpipe systems Where
required.
Standard inside
standpipe systems, complying with the requirements of
Chapter 15-16, shall be provided in all buildings exceeding
80 feet in height with the following exceptions:
(a) Institutional
Units. In institutional units, standpipes shall be
provided in all buildings more than four stories or 55 feet
in height.
(b) Stage
Blocks. In stage blocks, standpipes shall be provided on
each side of the stage, on each tier of dressing rooms, and
within 55 feet of all property rooms, store rooms or work
rooms.
(c) Storage
Structures. Standpipes shall not be required in grain
elevators or similar storage structures, where such
standpipes are ineffective owing to the type of structure
and inaccessibility of hose connections.
For the
purpose of determining standpipe requirements, the height of
a building shall be determined in accordance with the
provisions of Section 13-48-020. Towers, steeples, tanks and
similar structures not intended or used for human occupancy
shall not be considered in determining the height.
(d) This
section shall not apply to a building used as a business
unit or storage unit, in existence prior to January 20,
1950, which is equipped throughout with an approved system
of automatic sprinklers or is a fire resistive building of
Type IA, IB or IC construction, provided that a standpipe
system complying with Section 15-16-1190 is also provided in
the building.
(e) In
exhibition areas standpipes shall be provided regardless of
the height of the building and standpipe locations shall
provide complete coverage of the fire area with 100 foot
hose lengths and 30 foot hose streams.
(Prior code § 78-18)
13-196-200 Standard fire alarm system
requirements.
An approved fire
alarm system shall be provided as required in this section.
(a) A
standard fire alarm system meeting the requirements of this
chapter and Chapter 15-16 of this Code shall be provided in
the following occupancies:
(1) Institutional:
Buildings two stories or less in height with a floor area
which does not exceed 8,000 square feet shall be equipped
with a Class I system. Buildings over two stories in height
or with a floor area exceeding 8,000 square feet shall be
equipped with a Class II system;
(2) Type
I or Type II schools: Buildings over one story in height
shall be equipped with a Class I system;
Any Type I
school operating as or containing a day care center Class I,
as defined in Chapter 4-72, shall comply with fire alarm
system requirements applicable to Type III schools;
(3) Type
III schools: Class I system;
(4) Hotels:
Buildings of Types II, III or IV construction 80 feet or
less in height shall be equipped with a Class I system
except where 25 or fewer persons sleep above the second
floor;
(5) Single-room
occupancy buildings: new and existing single-room
occupancy buildings two stories or more in height, which are
not equipped with a complete automatic sprinkler system,
shall be equipped with a Class I fire alarm. The approved
standard Class I control equipment may use microprocessor
based program-controlled communication circuits when the
control equipment is of a type tested and conforming to
Underwriters Laboratories standard 864-1991 for the intended
use. The stored program (software) installed figuration for
such systems shall be incapable of change, except that a
manufacturers authorized technician may make changes for
proper system operation when such changes are approved by
the deputy commissioner of the fire prevention bureau. Any
changes, repairs or maintenance on such systems shall be
performed only by or under the direction of a licensed
supervising electrician.
(6) Dormitories:
Buildings two stories or more in height; except those where
25 or fewer persons sleep above the second floor, shall be
equipped with a Class I system;
(7)
Intermediate care facilities for the developmentally
disabled 15 or fewer persons, same as institutional uses.
(b) Hotels:
Buildings of Type 1 construction over four stories but not
over 80 feet in height shall be equipped with an approved
fire alarm system including smoke detectors, heat detectors
and water flow alarm devices installed in accordance with
NFPA 72A-1985 and annunciated visually and audibly for each
individual floor at a fire panel located near a main
entrance to the building. A one-way voice communication
system controlled from the fire panel location and meeting
the requirements of Section 13-196-210(e)(2) of this Code
shall be provided. Use of the one-way voice communication
system in a fire emergency by other than department of fire
personnel shall be prohibited.
(1) The
fire alarm system shall be zoned horizontally based on the
system design, but in no case shall there be less than one
zone per floor.
(2) The
fire alarm system shall be monitored by an Underwriters
Laboratories Inc. listed Central Station service or shall be
a Proprietary Protective Signalling System (installed in
accordance with National Fire Protection Association
Standard NFPA 72D-1986).
(3) A
fire panel consisting of fire alarm controls, annunciator
panel, and one-way voice communications system controls
shall be provided in a location approved by the bureau of
fire prevention. Fire panels installed prior to the passage
of this ordinance located on grade level in a readily
accessible location shall be accepted.
(4)
Plans for all systems to be installed shall be submitted to
the bureau of fire prevention for approval and systems used
shall meet the approval of the fire prevention bureau.
(c)
Notwithstanding any other provision of this Code to the
contrary, the revisions to the requirements of this chapter
and Chapter 15-16 contained in this amendatory ordinance
shall apply to schools and day care centers in existence on
the effective date of this amendatory ordinance beginning
July 1, 1991.
(d) The
requirements of subsection (a)(5) of this section shall be
enforced against all single-room occupancy buildings
effective June 30, 1995. All existing single-room occupancy
buildings which will require installation of a Class I alarm
system shall submit plans to the fire prevention bureau for
approval of such system on or before January 1, 1995.
(Prior code § 78-19;
Amend Coun. J. 9-8-86, p. 33588; Amend Coun. J. 6-27-90, p.
17613; Amend Coun. J. 5-4-94, p. 49750)
13-196-203 Life safety data sheet
Required.
(A) No later
than April 1, 2005, any owner of an existing building
exceeding 80 feet in height above grade shall file with the
fire department a life safety data sheet containing the
following information about the building; (1) the name of
the building owner of record, and, if applicable, the
building manager; (2) the address of the building; (3)
whether the building is residential or commercial or of
mixed use; (4) if the building is residential or of mixed
use, the number of dwelling units in the building; (5) the
number of stories in the building; (6) whether the building
is equipped with an automatic sprinkler system meeting any
or all of the requirements of Chapter 15-16 of this Code,
and identifying the areas so protected; and (7) whether the
building is equipped with a standard inside standpipe
system, a fire pump and a smokeproof tower.
(B) All
information contained in the life safety data sheet shall be
kept current. Any change in required information shall be
reported by the building owner to the fire department within
14 days after the change. This subsection shall be
enforceable against the building owner and against any
subsequent owner.
Any person who
violates the requirements of this section shall be fined not
less than $200.00 nor more than $500.00 for each offense.
Each day that a violation continues shall constitute a
separate and distinct offense.
(Added Coun. J.
12-15-04, p. 39962, § 1)
13-196-204 Voice communication systems in
existing buildings.
(A) Subject
to the exceptions listed below, no later than January 1,
2012, every existing building exceeding 80 feet in height
above grade shall be equipped with the following: (i) a
one-way voice communication system meeting the requirements
of Section 13-76-050(b); and (ii) a two-way voice
communication system meeting the requirements of Section
13-76-050(a); provided, however, that a telephone or other
two-way communication system connected to an approved
station, and installed pursuant to and in accordance with
Option 2 of Section 13-196-084(a), shall be deemed to
satisfy the requirements of item (ii) of this subsection.
(B) Neither a
one-way nor a two-way voice communication system shall be
required in the following buildings:
Exception
Number 1: Buildings that are classified as Class A-2,
Multiple Dwellings, and are for non- transient residential
use and are fully protected by automatic sprinklers.
Exception
Number 2: Institutional buildings and schools that have
an approved standard fire alarm system as required by
Section 15-16-110.
(C) A one-way
voice communication system shall not be required in the
following buildings:
Exception
Number 1: Non-transient residential buildings with an
existing occupant notification system if a detailed
description of the existing occupant notification system is
submitted to and approved by the commissioner of buildings
and the fire commissioner or by their designated
representatives. In order to be considered for approval
under this exception, and if approved under this exception,
the existing occupant notification system shall meet the
following criteria:
(a) the
system must be in continuous use and must be tested on a
monthly basis, or the system must have electronic
supervision to indicate operational deficiencies in the
system including, but not limited to, shorts, grounds and
breaks in the circuit wiring; and
(b) the
system must be audible throughout all required areas of the
building, or must produce within all dwelling units a
minimum sound level of 45 dBA within ten feet of any
existing occupant notification system device; and
(c) the
system must be able to transmit voice instructions without
delay; and
(d) the
system must be able to transmit voice instructions to all
required areas or to all dwelling units at the same time;
and
(e) the
system must be available for fire department use from a
central command location; and
(f) the
system is subject to field testing; and
(g)
replacement or modification of system components to meet
the above criteria is limited to 50 percent of the
reproduction cost of the existing occupant notification
system.
(D) A two-way
voice communication system shall not be required in the
following buildings:
Exception 1:
Buildings that are classified as Class A-2, Multiple
Dwellings, and are for non-transient residential use if the
building does not exceed 15 stories in height and contains
60 or fewer dwelling units as defined in Section 13-4-010.
(E) For
purposes of this section, non-transient residential means
a residential use other than a hotel, motel,
bed-and-breakfast establishment, dormitory, transitional
shelter, emergency shelter or other temporary residential
use.
(F) This
section shall be enforceable against the building owner and
against any subsequent owner.
(Added Coun. J.
12-15-04, p. 39962, § 2)
13-196-205 Automatic sprinkler system
installation in existing high-rise buildings.
Subject to the
exceptions listed below, every existing building exceeding
80 feet in height above grade shall be protected throughout
by an approved automatic sprinkler system meeting the
requirements of Chapter 15-16 of this Code unless otherwise
provided by Section 13-196-207. The owner of each such
building shall, no later than September 1, 2005, submit for
approval to the bureau of fire prevention a plan for
compliance with the requirements of this section. The
requirements of this section shall be enforceable against
the building owner and against any subsequent owner.
Every building
subject to the provisions of this section shall comply with
the following schedule for installation of an approved
automatic sprinkler system: one-third of the gross square
footage of the building shall be equipped with automatic
sprinklers by January 1, 2009; two-thirds of the gross
square footage of the building shall be equipped with
automatic sprinklers by January 1, 2013; and the entire
gross square footage of the building shall be equipped with
automatic sprinklers by January 1, 2017. Buildings subject
to any of the following exceptions 3 through 7, inclusive,
shall comply with the requirements of Section 13-196-206.
Exception
Number 1: An open-air parking facility meeting the
requirements of Section 13-96-920 of this Code.
Exception
Number 2: The open-air portions of a stadium.
Exception
Number 3: A building that is classified as a Class A-2,
Multiple Dwelling, and that is a non- transient residential
use. This exception includes (a) all approved auxiliary use
areas of the building other than parking garages; and (b)
any parking garage in the building that is used exclusively
by the buildings non- transient residential occupants and
their guests or by persons who, pursuant to a written lease
agreement, rent space in the buildings parking garage for
use by a designated motor vehicle in time increments of at
least one month in duration.
Exception
Number 4: The following portions of a building
classified as a mixed occupancy building:
(A) any
portion of a mixed occupancy building that is classified as
a Class A-2, non-transient residential use;
(B) any
approved auxiliary use area wholly contained within a Class
A-2, non-transient residential use portion of a mixed
occupancy building;
(C) any
parking garage in a mixed occupancy building that is used
exclusively by the buildings non- transient residential
occupants and their guests or by persons who, pursuant to a
written lease agreement, rent space in the buildings
parking garage for use by a designated motor vehicle in time
increments of at least one month in duration;
(D) any
portion of a mixed occupancy building, other than those
portions of the building classified as a Class A-2,
non-transient residential use, if all of the following
criteria are met:
(1) the
cumulative total of the buildings floor areas not
classified as a Class A-2, non-transient residential use
does not exceed ten percent of the total floor area of the
building. The floor areas of parking garages used
exclusively by the buildings non-transient residential
occupants and their guests shall be excluded from the
calculation of the buildings total floor areas not
classified as a Class A-2, non-transient residential use and
from the calculation of the total floor area of the
building; and
(2)
occupancy separations are provided in accordance with Table
13-56-280 as set out in Section 13-56-280 of this Code; and
(3) the
mixed occupancy building must be either of Type I,
fire-resistive construction or of Type II, non-combustible
construction; and
(4) all
of the exempted areas within the mixed occupancy building,
other than those portions of the building classified as a
Class A-2, non-transient residential use, are located in the
building at a floor level elevation that does not exceed 80
feet in height above average grade.
Exception
Number 5: A building designated as a Chicago Landmark
pursuant to Article XVII of Chapter 2-120 of this Code
unless the landmarked building is required to be equipped
with an automatic sprinkler system by other provisions of
this Code.
Exception
Number 6: A building within a landmark district
designated pursuant to Article XVII of Chapter 2-120 of this
Code and determined to be a contributing building unless the
contributing building is required to be equipped with an
automatic sprinkler system by other provisions of this Code.
Exception
Number 7: A building color-coded red or orange in the
Chicago Historic Resources Survey, published in 1996,
unless the building is required to be equipped with an
automatic sprinkler system by other provisions of this Code.
For purposes of
this section, non-transient residential means a
residential use other than a hotel, motel, bed-and-breakfast
establishment, dormitory, transitional shelter, emergency
shelter or other temporary residential use.
(Added Coun. J.
12-15-04, p. 39962, § 3)
13-196-206 Life safety evaluation of
existing high- rise buildings.
(A) No later
than January 1, 2005, the commissioner of buildings shall
adopt by rule and publish criteria for life safety
evaluations of all existing buildings exceeding 80 feet in
height above grade that are not required by Section
13-196-205 to be protected throughout by an approved
automatic sprinkler system. The criteria adopted pursuant to
this subsection shall provide sufficient protection to life
and safety of building occupants. The criteria shall be
developed based on a review of available resources,
including standardized building and safety codes and the
practices of other municipalities.
(B) The owner
of any building qualifying for any exception 3 through 7,
inclusive, of Section 13-196-205 shall have the building
evaluated for life safety by a licensed professional
engineer or by a licensed architect; provided, however, that
this requirement shall not apply to any building which is
protected throughout by a previously approved automatic
sprinkler system. The licensed engineer or architect shall
prepare a life safety evaluation of the building in
accordance with the requirements of this section and with
any rules and regulations promulgated thereunder. The life
safety evaluation shall be signed and sealed by the person
who prepared it and shall contain an explicit statement
acknowledging that the information contained therein is true
and complete.
(C) If, based
on the use of a scoring system described by rule to conduct
the life safety evaluation, the licensed professional
engineer or licensed architect determines that the building
achieves the minimum score required on the life safety
evaluation, the licensed engineer or architect shall certify
the evaluation as a life safety compliance plan and shall
give the life safety compliance plan to the building owner.
No later than January 1, 2006, the building owner shall
submit the life safety compliance plan to the department of
buildings and the bureau of fire prevention. The life safety
compliance plan shall be enforceable against the building
owner and against any subsequent owner.
(D) If, based
on the use of a scoring system described by rule to conduct
the life safety evaluation, the licensed professional
engineer or licensed architect determines that the building
does not achieve the minimum score required on the life
safety evaluation, the building owner shall, no later than
January 1, 2006, submit the life safety evaluation to the
department of buildings and the bureau of fire prevention
along with either: (1) a proposal to protect the building
throughout with an automatic sprinkler system meeting the
requirements of Chapter 15-16 of this Code unless otherwise
provided by Section 13-196-207, notwithstanding any
exceptions for which the building may have otherwise
qualified pursuant to Section 13-196-205, and using the
schedule for installation described in Section 13-196-205;
or (2) a proposal for achieving the minimum score required
on the life safety evaluation by making specified
modifications to the building.
Any proposal
submitted pursuant to this subsection shall be signed and
sealed by a licensed professional engineer or by a licensed
architect. In addition, any proposal submitted pursuant to
item (2) of this subsection shall contain (i) an explicit
statement by the licensed engineer or architect certifying
that if the modifications identified in the proposal are
fully implemented, the building will receive the minimum
score required on the life safety evaluation; and (ii) a
timetable for completion of those modifications to be phased
in over a stipulated period of years, but no later than
January 1, 2012, at which time the modifications identified
in the proposal shall be fully implemented. Any schedule for
installation or timetable required by this subsection shall
be enforceable against the building owner and against any
subsequent owner.
If, after
reviewing the certified proposal, the commissioner of
buildings and the deputy commissioner of the bureau of fire
prevention determine that the certified proposal, when fully
implemented, will enable the building to achieve the minimum
score required on the life safety evaluation, the
commissioner and deputy commissioner shall jointly accept
the certified proposal as a life safety compliance plan. The
life safety compliance plan shall be enforceable against the
building owner and against any subsequent owner.
(E) No permit
shall be issued for work on any existing building that is
the subject of a life safety compliance plan unless the
licensed architect or licensed engineer of record identified
in the permit application certifies in writing that the
permitted work will not reduce or otherwise negatively
impact the score of the life safety evaluation on which the
life safety compliance plan is based; nor shall any permit
be issued for work on a building whose owner is in violation
of any of the requirements of this section unless the permit
is necessary to cure the violation.
(F) Nothing
in this section shall be construed to waive any provision of
the Municipal Code of Chicago applicable to existing
buildings or to relieve any person from full compliance with
those provisions.
(Added Coun. J.
12-15-04, p. 39962, § 4)
13-196-207 Materials and installation
standards for retrofit fire protection systems.
In every existing
high-rise building subject to the requirements of Sections
13-196-204, 13-196-205 or 13-196-206 of this Code, the
following materials and installation standards shall apply
to newly installed fire protection systems:
(A) An
existing water supply that serves an existing fire
department wet standpipe system may also serve as the water
supply for retrofit sprinkler systems, provided the water
supply meets, non-simultaneously, the larger of either the
standpipe demand at the time of the original installation,
or the new sprinkler system demand including hose stream
allowance.
(B)
Notwithstanding the requirements of Sections 18-28-602.2.1
and 15-16-370, sprinkler piping and sprinklers shall meet or
exceed the requirements of NFPA 13-2002 and their respective
product listings issued by an approved independent
laboratory or agency.
(C) Automatic
sprinkler systems shall meet or exceed the requirements of
NFPA 13-2002 except that at least one sprinkler shall be
provided within the stairway enclosure at the landing
serving the door(s) to each floor.
(D) If
repairs or minor modifications are made to existing dry-pipe
sprinkler systems, the zoning of the system may remain as
originally installed.
(E)
Low-voltage electrical wiring risers for fire detection and
fire alarm notification systems may be installed in
stairways, notwithstanding the requirements of Section
15-8-180, if the wiring is in conduit and does not obstruct
the required egress width of a stairwell.
(F)
Low-voltage electrical branch wiring in horizontal runs for
voice communication systems may be installed without
conduit, unless required by other sections of this Code, if
the wiring (i) is limited combustible FHC 25/50 CMP; and
(ii) has a maximum Class 1 flame spread rating as defined in
Section 15-12-040; and (iii) has a smoke developed rating
not to exceed 50 when tested in accordance with ASTM-E 84.
(G)
Low-voltage electrical wiring for fire detection systems
may be run in the same conduit as low-voltage electrical
wiring for fire alarm notification systems, as permitted by
NFPA 72-2002 and the product listings of the wire and the
conduit issued by an approved independent laboratory or
agency.
(H)
Low-voltage fire detection equipment panels and low-voltage
fire alarm notification equipment panels may be installed in
the same panel box, as permitted by NFPA 72-2002 and the
products listing issued by an approved independent
laboratory or agency.
(I) Central
station monitoring of fire alarm systems may use digital
alarm communicators with constant supervision, as permitted
by NFPA 72-2002.
(Added Coun. J.
12-15-04, p. 39962, § 5)
13-196-208 Smokeproof towers in existing
high- rise buildings Fire shields.
If fire shields
in smokeproof towers are provided to protect openings of
balconies or vestibules in existing buildings exceeding 80
feet in height above grade, such fire shields shall comply
with the requirements of this section.
(A) Fire
shields shall comply with all applicable requirements for
fire windows as provided in Section 15-12-160.
(B) Fire
shields shall have an opening sash having a clear area not
less than as required in Section 13-160-380(c), arranged to
open automatically in case of fire to the full limit and to
be held securely in such open position. Provision shall be
made for the manual opening or closing of the sash.
(C) The
automatic opening of the sash shall be actuated by approved
devices located inside the building within five feet of the
door from the building to the vestibule or balcony and
located also on the ceiling of the vestibule or balcony.
Such devices shall be designed to operate as a result of
rate of temperature rise or when the surrounding air reaches
a temperature of 120 degrees Fahrenheit.
(D) Each fire
shield sash shall be tested annually to verify automatic
operation as required in subsection (c) of this section.
Testing shall be performed by an individual or organization
approved by the deputy commissioner in charge of the bureau
of fire prevention. Reports of the testing shall be filed
with the bureau by June 30 of each year.
(Added Coun. J.
12-15-04, p. 39962, § 6)
13-196-209 High-rise buildings Stairways
Doors Frames.
No later than
January 1, 2012, doors and frames in stairways in all
existing residential buildings and buildings of mixed
residential occupancy exceeding 80 feet in height above
grade shall have a fire resistance rating of at least one
hour.
(Added Coun. J.
12-15-04, p. 39962, § 7)
13-196-210 High rise fire systems.
Any existing or
preordinance building exceeding 80 feet in height designed
or used in whole or in part as a hotel shall be equipped
with a high rise fire system as required in this section.
(a) In
buildings equipped with an approved system of automatic
sprinklers, an approved fire alarm system including all
water flow alarm devices shall be required. Sprinklers may
be omitted in guest room closets not over 24 square feet in
area. Other areas not sprinkled, because of unreasonable
hardship or as permitted by Section 15-16-350 of this Code,
shall be protected by approved smoke detectors or other fire
detection measures approved by the bureau of fire
prevention. Detectors shall not be required in guest room
bathrooms. No automatic smoke detector shall be required in
guest room corridors nor elevator lobbies of existing
buildings having automatic sprinkler systems installed prior
to the passage of this ordinance on guest room floors except
that sprinklers may be omitted in guest room bathrooms over
55 square feet in area with noncombustible plumbing fixtures
and with walls and ceilings surfaced with noncombustible
materials.
(b) In
buildings not equipped with an approved system of automatic
sprinklers an approved fire alarm system, including smoke
detectors, heat detectors and water flow alarm devices,
shall be required. System devices shall be installed as
follows:
(1) As
required by Section 13-196-240 of this Code;
(2) Heat
detectors shall be installed in restaurants, meeting rooms
and lounges.
(c) The fire
alarm system shall be zoned horizontally based on the system
design, but in no case shall there be less than one zone per
floor.
(d) The fire
alarm system shall be a Proprietary Protective Signalling
System installed in accordance with National Fire Protection
Association Standard NFPA 72D-1986 or shall be monitored by
an Underwriters Laboratories Inc. listed Central Station
service.
(e) There
shall be two voice communication systems as follows:
(1) A
two-way fire department communications system providing
emergency two-way stations in each required stairwell at not
less than every fifth floor and at the fire panel. The
system shall be zoned not less than one zone per stairwell.
Systems installed prior to the passage of this ordinance
using phone jacks zoned by stairwell shall be accepted in
lieu of two-way stations.
(2) A
selecting one-way communication system with speakers in
passenger elevators, in elevator lobbies, in stairwells at
not less than every fifth floor, and in corridors at
intervals not exceeding 75 feet. Use of the one-way voice
communication system in a fire emergency by other than
department of fire personnel shall be prohibited. Zoning of
speakers shall be as follows: passenger elevators zoned by
elevator lobby; elevator lobbies and corridors zoned
horizontally based on the system design, but in no case less
than one zone per floor; stairwells zoned vertically by
stairwell. Approved elevator speaker intercom systems
installed prior to the passage of the ordinance shall be
accepted for communication to elevators as long as the
systems are maintained in good working order.
The two-way fire
department communication system may be combined with the
one-way system.
(f) A fire
panel consisting of fire alarm controls, annunciator panel,
and one- and two-way voice communications system controls
shall be provided in a location approved by the bureau of
fire prevention. Fire panels and controls installed prior to
the passage of this ordinance located on grade level in a
readily accessible location shall be accepted.
(g) Plans for
systems to be installed shall be submitted to the bureau of
fire prevention for approval and systems used shall meet the
approval of the fire prevention bureau.
(h) In
buildings of Type II, III or IV construction, an automatic
central alarm shall be installed and be audible throughout
the corridors of the building and shall be activated by the
sprinkler flow alarm and smoke detectors.
(Prior code § 78-19.1;
Added Coun. J. 9-8-86, p. 33588)
13-196-220 Class II standard fire alarm
systems.
A Class II
standard fire alarm system may be installed in lieu of a
Class I standard fire alarm system in any building when, in
the opinion of the division marshal in charge of the bureau
of fire prevention, the number of people involved and the
physical construction of such building makes a Class II
standard fire alarm system acceptable. Class II standard
fire alarm system shall comply with the provisions of
Chapter 15-16.
(Prior code § 78-20)
13-196-230 Floor area and height.
In every building
described in Section 13-196-200, as requiring a standard
fire alarm system, the area of such building shall be the
total area of the building and the height shall be the total
height of such building including the space used for
occupancies other than for institutional, school, hotel, or
single-room occupancies.
(Prior code § 78-21;
Amend Coun. J. 5-4-94, p. 49750)
13-196-240 Automatic fire detectors
Where required.
In every fire
alarm system required in this Code, automatic fire detectors
shall be installed as an integral part of a fire alarm
system in rooms or portions of the building as follows:
(a) In all
rooms where a flammable compressed gas or flammable liquid
as described in Chapters 4-112* and 15-24, other than fuel
oil for heating, is stored or used; also in shops and
storerooms where combustible material is stored or handled.
(b) In every
building used in part as an institutional building, school,
hotel, or single-room occupancy, an automatic fire detector
shall be installed in such portion or portions of the
building used for purposes other than institutional, school,
hotel, or single-room occupancy purposes, unless such
institutional building, school, hotel, or single-room
occupancy is separated from all other occupancies by a
separation with a fire resistive value as specified in
Section 13-56-280. Such automatic fire detectors shall be
installed, spaced and located in accordance with the
recommendations, based upon actual tests, prescribed by a
nationally recognized testing laboratory acceptable to the
fire prevention bureau.
(c) In every
storeroom, maintenance shop, fan room, mechanical equipment
room, laundry, linen room, janitor closet, kitchen and
storage area.
(d) Fire
alarm systems serving Type III schools, day care centers
Class II, and those Type I schools operating as or
containing a day care center Class I as defined in Chapter
4-72 shall include automatic detectors as follows:
1. Smoke
detectors shall be installed at each floor level, including
basements, of each interior stairwell up to and including
one level above the level of the school or day care center,
except in unoccupied attics.
2. Smoke
detectors shall be installed in front of doors to stairwells
from the school or day care center and at intervals of no
less than 30 feet in all corridors within or serving the
school or day care center.
3. Smoke
detectors shall be located in all lounges, recreation areas
and sleeping rooms.
4. Heat
detectors shall be installed in boiler rooms, kitchens and
combustible storage areas except where a sprinkler system
with a flow alarm connected to the fire alarm system is
installed in such rooms.
(e) In all
two-story buildings occupied as open plan schools, (a story
located below grade level shall be counted, if used for
other than building service purposes), approved automatic
fire detectors shall be installed throughout the building
and be interconnected to the school fire alarm system.
(f) In hotel
buildings over four stories, electrical equipment rooms,
guest room corridors and elevator lobbies shall be equipped
with automatic smoke detectors installed in accordance with
NFPA 72E-1984.
(g) In
single-room occupancy buildings, automatic heat detectors
shall be installed in each single-room occupancy unit, in
public corridors, and at each floor level in every interior
stairwell. In single- room occupancy buildings, smoke
detectors required by Section 13-196-100 of this Code need
not be connected to the fire alarm system, but shall be
permanently wired to the electrical wiring system of the
building.
(Prior code § 78-22;
Amend Coun. J. 9-8-86, p. 33588; Amend Coun. J. 6-27-90, p.
17613; Amend Coun. J. 5-4-94, 49750)
13-196-250 Permitted omission of
sprinklers, heat and smoke detectors.
No automatic heat
detector shall be required in any room or portion of a
building which is equipped with an approved installation of
automatic sprinklers and provided with a water flow alarm
which is connected to the fire alarm system. No automatic
smoke detector shall be required in guest room corridors nor
elevator lobbies of hotel buildings equipped with an
approved system of automatic sprinklers. Sprinklers may be
omitted in guest room closets not over 24 square feet in
area. Other areas not sprinklered, because of unreasonable
hardship or as permitted by Section 15-16-350 of the code,
shall be protected by approved smoke detectors or other fire
detection measures approved by the bureau of fire
prevention. Detectors shall not be required in guest room
bathrooms. No automatic smoke detector shall be required in
guest room corridors nor elevator to the lobbies of existing
buildings having automatic sprinkler systems installed prior
to the passage of this ordinance on guest room floors except
that sprinkler systems installed prior to the passage of
this ordinance on guest room floors except that sprinkler
systems may be omitted in guest room bathrooms over 55
square feet in area with noncombustible plumbing fixtures
and with walls and ceilings surfaced with noncombustible
materials.
(Prior code § 78-23;
Amend Coun. J. 9-8-86, p. 33588)
13-196-260 Fire extinguishers.
Standard fire
extinguishers shall be provided in accordance with the
provisions of Sections 15-16-620 through and including
15-16-680 of this Code.
(Prior code § 78-24)
13-196-270 Elevator recall.
All existing
buildings shall comply with the requirements of Section
18-30-2600.
(Added Coun. J.
6-14-95, p. 2820; Amend Coun. J. 1-10-01, p. 50236, § 2)
13-196-280 Reserved.
13-196-290 Pre-ordinance hotels.
Every
pre-ordinance hotel (built before July 7, 1957) more than
two stories and basement in height, having sleeping
accommodations for more than 25 persons above the second
story, and every pre-ordinance hotel of any capacity more
than four stories and basement in height, shall comply with
the requirements of Section 15-8-120 pertaining to the
protection of stairs, shafts and vertical openings, except
as follows:
(a) Enclosing
walls and partitions may be of construction providing fire
resistance of not less than one hour.
(b) Doors
required for protection of openings in enclosures may be
Class C fire doors of combustible material faced on both
sides with materials not less fire resistive than sheet
steel 18 gauge in thickness. Openings, if any, shall be
glazed with wire glass and shall not exceed 144 square
inches in area, except that existing openings not exceeding
1,296 square inches in area may be permitted.
(c) Where the
top or bottom riser in a stairwell is so located that the
vertical enclosures therein required will not be practical
to erect without unreasonable hardship, a horizontal cutoff
there shall be not more than three openings to dwelling
units or other nonpublic spaces on each floor, and such
dwelling units or nonpublic spaces shall be separated from
the corridor by partitions providing fire resistance of not
less than one hour with all openings protected with
self-closing Class C fire doors.
(Prior code § 78-27)
13-196-300 Institutional units.
In every
pre-ordinance institutional building, every room used for
the storage or application of anesthetics consisting of
flammable or explosive gases or mixtures, including
cyclopropane, ether chloride, ethylene, propylene, or any
flammable liquids, shall have safeguards for installation
and operation of such rooms and equipment as follows:
(a) Any
cylinders containing anaesthetizing gases or liquids shall
be plainly marked with the name of the substance which they
contain and shall comply with the requirements of the
Interstate Commerce Commission for such containers. Such
cylinders or containers shall not be stored in any operating
room. Approved regulators or gas flow devices shall be
provided for any such substances, except low pressure oxygen
containers.
No such
regulators or gas flow devices shall permit the intermixing
of gases by any error or manipulation.
(b) The
construction and equipment of operating rooms shall comply
with the applicable requirements of Section 13-80-040.
(Prior code § 78-28)
13-196-310 Roominghouses.
Every
roominghouse and every rooming unit shall be in compliance
with the minimum standards set forth in this chapter, except
as modified in Section 13-196-320.
(Prior code § 78-29)
13-196-320 Roominghouses Sanitary
facilities.
At least one
flush water closet, lavatory basin and bathtub or shower
shall be supplied for each ten persons or fraction of ten
within a roominghouse, including members of the family of
the owner if they share the use of the facilities.
All such
facilities shall be properly connected to required water and
sewage systems and shall be located within the dwelling so
as to be reasonably accessible from a common hall or
passageway to all persons sharing such facilities, and shall
not be more than one story removed from the rooming unit of
any occupant intended to share the facilities. In a
roominghouse in which rooms are let only to males, flush
urinals may be substituted for not more than 33 and
one-third percent of the required number of water closets.
In a roominghouse
where both sexes are accommodated, the water closets shall
be separately calculated, based on the occupancy of each
sex, except where not more than two water closets are
required.
(Prior code § 78-30)
13-196-330 Roominghouses Responsibility
of operator.
Every operator of
a roominghouse shall be responsible for the following
matters required by this chapter: extermination of insects,
rodents, or other pests in it or in its yard; disposal of
refuse by placing in it disposal facilities supplied by him;
hanging and removing all screens required; sanitary
maintenance of all walls, floors and ceilings; maintenance
of a sanitary condition in every part of the roominghouse;
and proper installation and repair of every facility.
(Prior code § 78-31)
13-196-340 Minimum requirements for
residential buildings General.
The provisions of
these Sections 13-196-350 through and including 13-196-640
are applicable to occupancy for residential purposes of any
building, whether or not such building was erected, altered
or converted in full or substantial compliance with
ordinances in force at the time of its erection, alteration,
or conversion and whether or not such building was erected,
altered or converted prior to the effective date of this
Code. The requirements imposed by these sections shall be in
addition to other applicable requirements for existing
buildings imposed by other provisions of Chapter 13-196.
(Prior code § 78-32)
13-196-350 Residential buildings Water
closet.
Every family unit
except as provided in Section 13-196-380 shall contain
within its walls, a room, separate from the habitable rooms,
which affords privacy to a person and is equipped with a
flush water closet.
(Prior code § 78-33)
13-196-360 Residential buildings
Lavatory.
Every family unit
except as provided in Section 13-196-380 shall contain
within its walls a lavatory basin located in the same room
as the required water closet, or as near to that room as
practicable.
(Prior code § 78-34)
13-196-370 Residential buildings Bathtub
or shower.
Every family unit
except as provided in Section 13-196-380 shall contain
within its walls a room, separate from the habitable rooms,
which affords privacy to a person in the room and which is
equipped with a bathtub or shower.
(Prior code § 78-35)
13-196-380 Residential buildings
Limitations on sharing sanitary facilities.
The occupants of
not more than two-family units which are located in the same
dwelling, may share a single flush water closet, a single
lavatory basin, a single bathtub or shower if:
(a) The
facilities to be shared are within a room or rooms on the
same floor as the family units and are accessible to the
occupants of each family unit without going through the
family unit of another person or outside the dwelling; and
(b) Neither
of the two-family units contains more than two habitable
rooms nor more than 500 square feet of floor area, excluding
of the number of rooms and from floor area any kitchen of
less than 70 square feet of the floor area.
(Prior code § 78-36)
13-196-390 Residential buildings Kitchen
sink.
Every family unit
shall contain within its walls a kitchen sink.
(Prior code § 78-37)
13-196-400 Residential buildings Heating
facilities.
Every family unit
shall have heating facilities which are capable of safely
and adequately heating all habitable rooms, bathrooms and
water closet compartments within its walls to a temperature
of at least 65 degrees Fahrenheit, when the outside
temperature is ten degrees below zero Fahrenheit. Gas
appliances designed primarily for cooking or water heating
purposes shall not be considered as heating facilities
within the meaning of this section. Portable heating
equipment employing flame and the use of gasoline as a fuel
does not meet the requirements of this section and is
prohibited. The owner may require that the occupant shall
provide the required heating facilities at the occupants
expense but such agreement or requirement does not relieve
the owner from responsibility for the presence of such
heating equipment in the family unit.
(Prior code § 78-38)
13-196-410 Residential buildings Heat to
be furnished.
Every family unit
or rooming unit to which heat is furnished from a heating
plant used in common for the purpose of heating the various
rooms of the dwelling shall be supplied with heat from
September 15th of each year to June 1st of the succeeding
year so that the occupants of a family unit or rooming unit
may secure, without such undue restriction of ventilation as
to interfere with proper sanitary conditions, a minimum
temperature of 68 degrees at 8:30 a.m. and thereafter until
10:30 p.m. and 66 degrees at 10:30 p.m. and thereafter until
8:30 a.m. averaged throughout the family unit or rooming
unit.
(Prior code § 78-39;
Amend Coun. J. 2-25-88, p. 10733; Amend Coun. J. 3-9-05, p.
43526)
13-196-420 Residential buildings Cold
and hot water lines.
Every kitchen
sink, lavatory and bathtub or shower required shall be
connected with hot and cold water lines. The hot water lines
shall be connected with water heating facilities which are
capable of heating water to such a temperature as to permit
water to be drawn at every required outlet at a temperature
of not less than 120 degrees Fahrenheit even when the
heating facilities required by this Code are not in
operation.
(Prior code § 78-40)
13-196-430 Residential buildings Hot
water to be furnished.
Every family unit
or rooming unit to which hot water is furnished from water
heating facilities used in common shall be supplied with hot
water throughout the year so that the occupants may draw
water at every hot water outlet between the hours of 6:00
a.m. and 10:30 p.m. of a minimum temperature of 120 degrees
Fahrenheit.
(Prior code § 78-41)
13-196-440 Gas-fired appliances.
All gas-fired
heating, cooking and other appliances and gas-fired water
heaters, shall conform to the requirements in Sections
13-152-390* through 13-152-440* and 13-180-100* and
13-180-230* of the building provisions of this Code
concerning installation, vents and flues.
(Prior code § 78-42)
13-196-450 Residential buildings Hall
and stairway lighting.
Every public hall
and stairway in every dwelling having more than one family
unit shall be adequately lighted at all times, except that
in a two-family dwelling an adequate lighting system which
may be turned on when needed by conveniently located light
switches shall be permitted instead of a full-time lighting
system.
(Prior code § 78-43)
13-196-460 Residential buildings Storage
beneath stairways.
There shall be no
closets or storage of any kind beneath stairways in any
dwelling containing two or more family units or in any
roominghouse unless the stair complies with the fire
resistive requirements of Sections 15-8-120 to 15-8-180
inclusive, or unless the stairs and storage space are
separated by noncombustible materials having a fire rating
of not less than one hour. No combustible or flammable
materials, fluids, or compounds shall be placed, stored or
kept in any place inside or outside of any building where
the ignition or burning of such materials, fluids, or
compounds would obstruct or render hazardous the egress from
any family unit or from the building.
(Prior code § 78-44)
13-196-470 Residential buildings Space,
use and location Applicability of provisions.
No person shall
occupy or cause or permit the continued occupancy of any
family unit which does not comply with the standards of
occupancy set forth in Sections 13-196-480 through and
including 13-196-520 of this chapter.
The provisions of
Sections 13-196-480 through and including 13-196-520 shall
not be applicable to single- family dwellings occupied only
by an owner and persons within the family relationship.
(Prior code § 78-45)
13-196-480 Residential buildings Space
requirements.
Every family unit
shall contain at least 125 square feet of floor area for
each of the first two occupants, and at least 100 square
feet of each of the next two occupants, and at least 75
square feet for each additional occupant. For the purpose of
this section, floor area is the area within the perimeter of
the space or building occupied by the family unit, not
including elevators, stairs, or other shaft enclosures.
(Prior code § 78-46)
13-196-490 Residential buildings Space
requirements Sleeping rooms.
In every family
unit and every rooming unit, every room occupied for
sleeping purposes by one occupant shall contain at least 70
square feet of floor area, or if of original configuration
need only comply with the regulations in effect at the time
of its construction. Every room occupied for sleeping
purposes by more than one occupant shall contain at least 50
square feet of floor area for each occupant 12 years of age
and over and at least 35 square feet of floor area for each
occupant under 12 years of age. For the purpose of this
section a person under two years of age shall not be counted
as an occupant.
(Prior code § 78-47)
13-196-500 Residential buildings Access
to water closets.
Every room used
exclusively as a bedroom shall have access to at least one
water closet without passing through another room used
exclusively as a bedroom.
(Prior code § 78-47)
13-196-510 Residential buildings Ceiling
heights.
At least one-half
of the floor area of every habitable room shall have a
ceiling height of not less than seven feet; and the floor
area of that part of any room where the ceiling height is
less than five feet shall not be considered as part of the
floor area in computing the total floor area of the room for
the purpose of determining the maximum permissible occupancy
thereof. However, in any room, beams or furred spaces
constituting not more than 25 percent of the ceiling area,
may have a height of not less than six feet.
(Prior code § 78-49)
13-196-520 Residential buildings
Basement units.
A basement space
used as a habitable room or family unit shall comply with
the following:
1. The floor
depth below grade is not limited if the floors and walls are
impervious to leakage of underground and surface runoff
water and are protected against dampness.
2. The
required minimum window area is located entirely above the
finished elevation of the ground adjoining the building wall
in which the windows are located.
(Prior code § 78-50)
13-196-530 Residential buildings
Foundations, exterior walls and roofs Maintenance.
The foundation,
exterior walls, and exterior roof shall be substantially
watertight and protected against rodents, and shall be kept
in sound condition and repair:
(a) The
foundation elements shall adequately support the building at
all points.
(b) Every
exterior wall shall be free of holes, breaks, loose or
rotting boards or timbers, and any other conditions which
might admit rain, or dampness to the interior portions of
the walls or to the exterior spaces of the dwelling.
(c) The roof
shall be tight and have no defects which admits rain and
roof drainage shall be adequate to prevent rain water from
causing dampness in the walls.
(d) The
dwelling shall be in a rat-stopped condition, in accordance
with Sections 7-28-660 through 7-28-730 of this Code, and
shall be adequately protected against the entry of other
rodents.
(e) All
cornices, rustications, quoins, moldings, belt courses,
lintels, sills, oriel windows, pediments and similar
projections shall be kept in good repair and free from
cracks and defects which make them hazardous and dangerous.
(Prior code § 78-51)
13-196-540 Residential buildings Floors,
interior walls and ceilings Maintenance.
Every floor,
interior wall, and ceiling shall be kept in sound condition
and good repair and further,
(a) Every
floor shall be free of holes and wide cracks which might
admit rodents or which constitute a possible accident
hazard.
(b) Every
floor shall be free of loose, warped, protruding, or rotting
floor boards.
(c) Every
interior wall and ceiling shall be free of holes and large
cracks.
(d) All
interior walls, ceilings and interior woodwork shall be free
of flaking, peeling, chipped or loose paint, plaster or
structural material.
(e) Plaster,
paint and other surface materials shall be of such character
as to be easily cleanable, and are reasonably smooth, clean
and tight.
(f) Every
toiletroom and bathroom floor surface shall be substantially
impervious to water and be capable of being maintained
easily in a clean and sanitary condition.
(Prior code § 78-52)
13-196-550 Residential buildings
Windows, doors and hatchways Maintenance.
Every window,
exterior door, and basement hatchway shall be substantially
tight, and shall be kept in sound condition and repair, and
(a) Every
window shall be fully supplied with window panes which are
without open cracks or holes.
(b) Every
window sash shall be in good condition and fit reasonably
tight within its frame.
(c) Every
window, other than a fixed window, shall be capable of being
easily opened and shall be held in position by window
hardware.
(d) Every
exterior door, door hinge, and door hatch shall be in good
condition.
(e) Every
exterior door, when closed, shall fit reasonably well within
its frame.
(f) Every
window, door, and frame shall be constructed and maintained
in such relation to the adjacent wall construction as
completely to exclude rain, and substantially to exclude
wind from entering the dwelling.
(g) Every
basement hatchway shall be so constructed and maintained as
to prevent the entrance of rodents, rain, and surface
drainage water into the dwelling.
(h) Every
door available as an exit as required by this chapter shall
be capable of being opened from the inside, easily and
without the use of a key.
(Prior code § 78-53)
13-196-560 Residential buildings
Screens.
Screens shall be
supplied to the following extent:
(a) Every
basement or cellar window which is openable shall be
supplied with a heavy wire screen or hardware cloth of not
less than four mesh per inch which fits tightly and is
securely fastened to the frame, or with any other material
affording equivalent protection against the entry of
rodents.
(b) From
April 15th to November 15th of each year, every door opening
directly from any family unit to the outdoors and every
window, or other outside openings used for ventilation
purposes, shall be supplied with a screen of not less than
16 mesh per inch and every screen door shall have a
self-closing device in good working condition. Except for
existing screens, which shall not be removed without the
written consent of the person entitled to possession of the
unit, no screens shall be required for a family unit on a
floor above the fourth floor, unless required by the
department of buildings and fire department when unusual
circumstances of insect prevalence exists.
(Prior code § 78-54;
Amend Coun. J. 9-13-89, p. 4604; Amend Coun. J. 6-27-90, p.
17617)
13-196-570 Residential buildings
Stairways and porches Maintenance.
Every stairway,
inside or outside of the dwelling and every porch, shall be
kept in safe condition and sound repair and:
(a) Every
flight of stairs and every porch floor shall be free of
holes, grooves, and cracks, which are large enough to
constitute possible accidents hazards.
(b) Every
stairwell and every flight of stairs, which is more than two
risers high, shall have rails not less than two and one-half
feet high, measured vertically from the nose of the tread to
the top of the rail; and every porch which is more than two
risers high shall have rails not less than three and
one-half feet above the floor of the porch.
(c) Every
rail and balustrade is firmly fastened and is maintained in
good condition.
(d) No flight
of stairs shall have settled more than one inch out of its
intended position or have pulled away from supporting or
adjacent structures.
(e) No flight
of stairs shall have rotting, loose or deteriorating
supports.
(f) The riser
height and the tread width of each flight of stairs shall be
uniform.
(g) Every
stair tread shall be sound and be securely fastened in a
substantially level position.
(h) Every
stair tread shall be strong enough to bear a concentrated
load of at least 400 pounds without danger of breaking.
(i) Every
porch shall have a sound floor.
(j) No porch
shall have rotting, loose or deteriorating supports.
(Prior code § 78-55)
13-196-580 Residential buildings
Basements and cellars Maintenance.
Every basement
and every cellar shall be maintained in a safe and sanitary
condition, and:
(a) Water
shall not be permitted to accumulate or stand on the floor.
(b) All sewer
connections shall be properly trapped.
(c) All
cellar and slab drains shall be covered with grating.
(d) Junk,
rubbish, and waste shall not be permitted to accumulate to
such an extent as to create fire hazards or to endanger
health or safety.
(Prior code § 78-56)
13-196-590 Residential buildings
Facilities, equipment, chimneys Maintenance.
Every supply
facility, piece of equipment or utility, and every chimney
and chimney flue, shall be installed and maintained in a
safe and sound working condition.
(Prior code § 78-57)
13-196-600 Residential buildings Lot
grading and drainage.
Every yard,
court, vent passageway, and other portions of the lot on
which the dwelling stands shall be graded and drained so as
to prevent the accumulation of stagnant water on any such
surface.
(Prior code § 78-58)
13-196-610 Residential buildings
Responsibilities of owners and occupants General.
In addition to
other applicable provisions of this Code, owners and
occupants of residential buildings shall comply with the
respective responsibilities imposed upon them by Sections
13-196-620 through and including 13-196-640 of this chapter.
(Prior code § 78-59)
13-196-620 Residential buildings
Responsibilities of occupants.
Every occupant of
a family unit must:
(a) Keep that
part of the family unit which he occupies and controls in a
clean, sanitary and safe condition;
(b) Keep all
plumbing and other fixtures required by this chapter,
whether or not supplied by the landlord, in a clean and
sanitary condition, and if supplied by the landlord, must
use reasonable care in the proper use and operation thereof;
(c) If a
single-family dwelling unit, exterminate any insects,
rodents or other pests therein or on the premises and, if a
family unit in a dwelling containing more than one family,
exterminate such insects, pests, and rodents whenever his
family unit is the only one in the dwelling infested, except
as provided in Section 13-196-630 (c);
(d) Dispose
of all garbage and other refuse only in the containers
required by Section 7-28-220 of the code and must place such
refuse in the containers in a clean and sanitary manner;
(e) Hang and
remove all screens required for the family unit by this
chapter unless the owner has agreed to supply such service;
(f) Not place
on the premises any material which may cause a fire hazard
or otherwise endangers the health or safety of any occupant
of such dwelling, nor place in storage on the premises any
furniture, equipment, or material which harbors insects,
rodents, or other pests;
(g) Not
permit any family unit let to him to be occupied so that any
occupancy resulting therefrom violates any of the provisions
of this chapter;
(h) Provide
heating facilities for that part of the family unit he
occupies unless such facilities are provided by the owner.
Gas appliances designed to be used primarily for cooking or
water heating purposes shall not be considered as heating
facilities within the meaning of this section.
(Prior code § 78-60)
13-196-630 Residential buildings
Responsibilities of owner or operator.
Every owner or
operator must:
(a) Comply
with the requirements imposed on him by this chapter;
(b) Maintain
in a clean, sanitary and safe condition the shared or public
areas of the dwelling or premises, and maintain and repair
any equipment of a type specified in this Code which he
supplies or is required to supply;
(c)
Exterminate any insects, rodents or other pests in any
family unit, if infestation is caused by the failure of the
owner or operator to maintain the dwelling in a ratproof or
reasonable insect-proof condition, and he must exterminate
such pests in any family unit in the dwelling, regardless of
the cause of infestation, if infestation exists in two or
more of the family units in the dwelling or in the shared or
public parts of any dwelling containing two or more family
units; and
(d) Supply
and maintain the facilities for refuse disposal which are
required of him by Section 7-28-220.
(Prior code § 78-61)
13-196-640 Residential buildings
Liability to city.
An owner remains
liable to the city for violation of duties imposed upon him
by this chapter even though:
(a) An
obligation is also imposed on the occupant by this chapter;
or
(b) The owner
has by agreement imposed on the occupant the duty of
furnishing required equipment or of complying with this
chapter.
(Prior code § 78-62)
13-196-641 Application of certain
sections.
The provisions of
Sections 13-196-530 through 13-196-640, inclusive, shall
apply to all existing buildings, regardless of use or
occupancy.
(Added Coun. J.
7-25-01, p. 64897, § 12)
13-196-650 Pre-ordinance conversion to
existing buildings Applicability.
A pre-ordinance
(built before July 8, 1957) residential building or building
of mixed residential occupancy not complying with the
requirements in force and applicable to the building at the
time of its conversion may, if permitted by the Zoning
Ordinance, be altered so as to legalize the present number
of dwelling units provided such building complies with all
the provisions of Chapter 13-196. For conversions which have
added only one additional dwelling unit over the original
number permitted, the provisions of Section 13-196-740 shall
apply.
(Prior code § 78-63)
13-196-660 Conversion of pre-ordinance
buildings Height limits.
The said
pre-ordinance building shall be not more than four stories
in height if of ordinary construction, or two stories in
height if of frame construction.
(Prior code § 78-64)
13-196-670 Stairwells.
New and existing
stairwells are to be separated from all other parts of the
building with partitions providing a fire resistance rating
of not less than one hour. Stairwells, doors, and frames are
to comply with Section 15-8-180. Stair soffits shall be
protected with wood lath and plaster, or one hour
construction.
(Prior code § 78-65)
13-196-680 Corridors.
Partitions
enclosing public corridors must have a fire resistance
rating of not less than one hour, and corridor doors and
frames are to comply with Section 13-64-020 (b).
(Prior code § 78-66)
13-196-690 Dwelling separations.
Partitions
separating dwelling units or between dwelling units and
other occupancies, including heating plants must be of
one-hour-fire-rated construction.
(Prior code § 78-67)
13-196-700 Partitions.
All partitions
are to be of original construction or of a
half-hour-fire-rated construction. Existing partitions may
be altered or replaced with material allowed in the original
structure.
(Prior code § 78-68)
13-196-710 Basement ceiling construction.
Floor
construction over the basement shall be a minimum of a half
hour construction when the building contains three dwelling
units or more.
(Prior code § 78-69)
13-196-720 Heating plants.
Furnaces or other
heating plants shall be enclosed with a minimum of a half
hour construction when the building contains three dwelling
units or more.
(Prior code § 78-70)
13-196-730 Light and ventilation.
Light and
ventilation requirements are to comply with code provisions
in effect at the time the building was originally
constructed or they may comply with present requirements for
new construction except as follows:
(a) A kitchen
with a floor of less than 70 square feet may be without
either mechanical or natural ventilation if there is an
opening of not less than 32 square feet between the kitchen
and another room in the same family unit and if the room
into which the kitchen opens meets the ventilation
requirements of this Code.
(b) Every
toilet room and bathroom shall have adequate ventilation
which may be either an openable window with an operable area
of five percent of the floor area, mechanical ventilation
complying with the requirements of Chapter 13-176*, or a
gravity vent flue constructed with incombustible leading to
the roof of the building, or a combination of any of these.
The gravity vent shall be computed at an aggregate clear
area of not less than five percent of the floor area of the
room, with a minimum area of at least 120 square inches.
Gravity vents shall be provided with a weather cap,
directional vane, or rotary type ventilation on roof.
(Prior code § 78-71)
13-196-740 One additional dwelling unit
over original allowed Conditions.
A pre-ordinance
(built before July 8, 1957) residential building or building
of mixed residential occupancy, not complying with the
requirements in force and applicable to the building at the
time of its conversion, may be altered so as to legalize one
dwelling unit, in addition to the number of dwelling units
originally authorized, providing that said unit was
determined by the office of the zoning administrator or the
zoning board of appeals to have existed prior to July 8,
1957, and provided such building complies with the other
provisions of this chapter. Such conversion need not comply
with the requirements of the following specific provisions
of this chapter:
(a) Section
13-196-660 (height limits); however, in frame buildings,
four or more levels of living space shall be prohibited and
in buildings of ordinary construction, with or without attic
living space, five or more levels shall be prohibited;
(b) Section
13-196-050; however, all dwelling units must comply with the
exit provisions of Chapter 13-160 except basement dwelling
units may have a second exit through a room containing a
heating plant;
(c) Section
13-196-670 (stairwell enclosures);
(d) Section
13-196-680 (corridor enclosures);
(e) Section
13-196-690 (dwelling separations);
(f) Section
13-196-710 (basement ceiling construction); however, if the
basement contains a dwelling unit the entire basement
ceiling construction is to be wood lath and plaster of half
hour construction;
(h) Section
13-196-720 (heating plants); however, basement apartments
are to be separated from heating plants with partitions of
one hour construction.
(Prior code § 78-72;
Amend Coun. J. 6-14-95, p. 2841)
13-196-750 Heat required.
It shall be the
duty of every person owning or controlling the heating plant
which furnishes heat to any factory or workshop, to maintain
a temperature within such factory or workshop of not less
than 68 degrees Fahrenheit without such undue restriction of
ventilation as to interfere with proper sanitary conditions
therein; provided, however, that this requirement shall not
apply to any factory or workshop where the business
conducted therein is of such a nature that a higher or lower
temperature than 68 degrees Fahrenheit is necessary or
expedient for the work, or manufacturing processes of such
business; and provided, further, that in all such cases,
when such higher or lower temperature is necessary or
expedient, the moisture content of the air shall be
increased where the temperature is maintained below 68
degrees Fahrenheit or decreased where the temperature is
maintained above 68 degrees Fahrenheit in the proper amount
to maintain a wet bulb temperature between 54 degrees and 58
degrees Fahrenheit, and in the case of special manufacturing
processes where it is necessary or expedient to maintain a
wet bulb temperature below or above the extremes herein set
forth, the commissioner of buildings shall prescribe and
enforce such reasonable precautions and safeguards as will
meet the requirements of such special manufacturing
processes without endangering the health of the occupants of
such factory or workshops. The manner of determining the
temperature in all cases where the temperature to be
maintained is 68 degrees Fahrenheit shall be the same as in
Section 5-4-060, and in all other cases shall be in such
practical manner as the commissioner of buildings may
determine.
It shall be the
duty of any person owning or controlling the heating plant
which furnishes heat to any office, store, or other place of
employment to maintain a temperature therein of not less
than 68 degrees Fahrenheit without such undue restriction of
ventilation as to interfere with proper sanitary conditions
therein, between the hours of 8:00 A.M. and 6:00 P.M., from
October 1st of each year to June 1st of the succeeding year,
Sundays and full legal holidays excepted.
The provisions of
this section shall apply to every existing building or
portion thereof containing a factory or workshop, office,
store or other place of employment, as the case may be.
(Prior code § 96-27;
Amend Coun. J. 3-31-04, p. 20916, § 2.6)
13-196-760 Endangering health of
employees.
Every owner or
person in charge of any existing factory shall cause the
temperature of every part thereof in which any person may
work to be so maintained, and such accommodations and
safeguards to be provided as not to cause, by reason of the
want thereof or by reason of the condition of any such
factory or its appurtenances, unnecessary danger or
detriment to the health of any person employed therein.
(Prior code § 96-28;
Amend Coun. J. 3-31-04, p. 20916, § 2.7)
|