|
CHAPTER 13-196 - EXISTING BUILDINGS
MINIMUM REQUIREMENTS
13-196-010
Application.
13-196-020
Occupancy.
13-196-030
Structural stability.
13-196-031
Maintenance of exterior walls and enclosures Definitions.
13-196-032
Maintenance of exterior walls and enclosures Application.
13-196-033
Maintenance of exterior walls and enclosures Maintenance
and reporting required.
13-196-034
Maintenance of exterior walls and enclosures Critical
examination program.
13-196-035
Ongoing inspection and repair program.
13-196-036
Maintenance of exterior walls and enclosures Unsafe
exterior walls and enclosures.
13-196-036.5
Maintenance of exterior walls and enclosures Reports to
the commissioner.
13-196-037
Ongoing inspection and repair program.
13-196-038
Fines and penalties.
13-196-038.5
Rules and regulations.
13-196-040
Floor loading.
13-196-050
Exit requirements.
13-196-060
Exits Generally.
13-196-070
Exits Types.
13-196-080
Passageways and exits to be unobstructed.
13-196-084
Stairwell re-entry in existing buildings.
13-196-085
Stairwell identification.
13-196-086
Area of rescue assistance identification.
13-196-090
Exit, stairway, fire escape and directional signs.
13-196-100
Smoke detectors Where required.
13-196-110
Smoke detectors Installation near sleeping rooms and in
living levels.
13-196-120
Smoke detectors Interior stairwell installation.
13-196-130
Smoke detectors Standards.
13-196-140
Smoke detectors Owner/tenant responsibilities.
13-196-150
Smoke detectors Unlawful acts.
13-196-160
Smoke detectors Multifamily and single-family
installation When.
13-196-165
Carbon monoxide detectors.
13-196-170
Self-closing devices required for corridor doors.
13-196-180
Sprinkler systems Where required.
13-196-190
Standpipe systems Where required.
13-196-200
Standard fire alarm system requirements.
13-196-203
Life safety data sheet Required.
13-196-204
Voice communication systems in existing buildings.
13-196-205
Automatic sprinkler system installation in existing
high-rise buildings.
13-196-206
Life safety evaluation of existing high-rise buildings.
13-196-207
Materials and installation standards for retrofit fire
protection systems.
13-196-208
Smokeproof towers in existing high- rise buildings Fire
shields.
13-196-209
High-rise buildings Stairways Doors Frames.
13-196-210
High rise fire systems.
13-196-220
Class II standard fire alarm systems.
13-196-230
Floor area and height.
13-196-240
Automatic fire detectors Where required.
13-196-250
Permitted omission of sprinklers, heat and smoke detectors.
13-196-260
Fire extinguishers.
13-196-270
Elevator recall.
13-196-280
Reserved.
13-196-290
Pre-ordinance hotels.
13-196-300
Institutional units.
13-196-310
Roominghouses.
13-196-320
Roominghouses Sanitary facilities.
13-196-330
Roominghouses Responsibility of operator.
13-196-340
Minimum requirements for residential buildings General.
13-196-350
Residential buildings Water closet.
13-196-360
Residential buildings Lavatory.
13-196-370
Residential buildings Bathtub or shower.
13-196-380
Residential buildings Limitations on sharing sanitary
facilities.
13-196-390
Residential buildings Kitchen sink.
13-196-400
Residential buildings Heating facilities.
13-196-410
Residential buildings Heat to be furnished.
13-196-420
Residential buildings Cold and hot water lines.
13-196-430
Residential buildings Hot water to be furnished.
13-196-440
Gas-fired appliances.
13-196-450
Residential buildings Hall and stairway lighting.
13-196-460
Residential buildings Storage beneath stairways.
13-196-470
Residential buildings Space, use and location
Applicability of provisions.
13-196-480
Residential buildings Space requirements.
13-196-490
Residential buildings Space requirements Sleeping
rooms.
13-196-500
Residential buildings Access to water closets.
13-196-510
Residential buildings Ceiling heights.
13-196-520
Residential buildings Basement units.
13-196-530
Residential buildings Foundations, exterior walls and
roofs Maintenance.
13-196-540
Residential buildings Floors, interior walls and ceilings
Maintenance.
13-196-550
Residential buildings Windows, doors and hatchways
Maintenance.
13-196-560
Residential buildings Screens.
13-196-570
Residential buildings Stairways and porches
Maintenance.
13-196-580
Residential buildings Basements and cellars
Maintenance.
13-196-590
Residential buildings Facilities, equipment, chimneys
Maintenance.
13-196-600
Residential buildings Lot grading and drainage.
13-196-610
Residential buildings Responsibilities of owners and
occupants General.
13-196-620
Residential buildings Responsibilities of occupants.
13-196-630
Residential buildings Responsibilities of owner or
operator.
13-196-640
Residential buildings Liability to city.
13-196-641
Application of certain sections.
13-196-650
Pre-ordinance conversion to existing buildings
Applicability.
13-196-660
Conversion of pre-ordinance buildings Height limits.
13-196-670
Stairwells.
13-196-680
Corridors.
13-196-690
Dwelling separations.
13-196-700
Partitions.
13-196-710
Basement ceiling construction.
13-196-720
Heating plants.
13-196-730
Light and ventilation.
13-196-740
One additional dwelling unit over original allowed
Conditions.
13-196-750
Heat required.
13-196-760
Endangering health of employees.
13-196-010
Application.
Every existing building shall comply with the code
requirements in force and applicable to such building, at
the time of its construction or alteration, and shall also
comply with such provisions of this chapter which are
specifically made applicable to all existing buildings.
However, nothing in this chapter shall be interpreted to
prevent the application of the Chicago Zoning Ordinance,
Title 17 of this Code.
(Prior code § 78-1)
13-196-020
Occupancy.
No person shall occupy as an owner-occupant, or shall let
or hold out to another for occupancy, any building which
does not comply with the requirements of this chapter.
(Prior code § 78-2)
13-196-030
Structural stability.
If there is any doubt as to the structural stability of any
building or structure, or parts thereof, the building
commissioner may request such building or structure, or
parts thereof, to be critically examined by a licensed
architect or registered structural engineer employed by such
owner, agent or person in charge, possession or control of
any such building, structure, or part thereof.
Said licensed architect or registered structural engineer
shall render a report in writing, showing the structural
condition of the building, structure or part thereof. Two
copies of the report shall in turn be submitted to the
building commissioner. One copy of said report shall, if
satisfactory, be retained by the building commissioner, and
one be returned to the owner, agent or person in charge,
possession or control of said building, structure or parts
thereof, bearing a stamp of approval signed by said building
commissioner.
(Prior code § 78-3;
Amend Coun. J. 9-13-89, p. 4604)
13-196-031
Maintenance of exterior walls and enclosures Definitions.
These terms shall have the following meanings when used in
Sections 13-196-031 through 13-196-036, which sections shall
be known as the minimum requirements for maintenance of
exterior walls and enclosures, as further clarified by such
rules and regulations promulgated by the commissioner of
buildings pursuant to Section 13-196-037:
Critical examination shall mean a close-up visual
examination of the condition of all elevations of the
exterior walls and enclosure. For buildings constructed of
material other than terra cotta, the examination may be
satisfied by scaffolding utilizing alternate drops to cover
at least 50 percent of the area of each elevation, and
including all corners of the building. For buildings
constructed of terra cotta material, the examination shall
cover the entire area of all elevations. All examinations
shall be performed by or under the direct supervision of a
professional employed by the owner/agent for the purpose of
determining if remedial work is required.
Ongoing inspection and repair shall mean a program of
bi-annual inspections by a professional retained by the
owner/agent, with accompanying report by the professional to
the commissioner of buildings and repair work by the
owner/agent as necessary.
Ornamental Piece shall mean any terra cotta, stone or
other decorative addition to a building defined in Section
13-196-032 that is primarily secured to the substrate by a
metal fastener.*
Owner/agent shall mean the owner, agent or person in
charge, possession or control of the building.
Professional shall mean an Illinois licensed architect or
Illinois licensed structural engineer.
(Added Coun. J.
7-31-02, p. 91358, § 1; Amend Coun. J. 9-4-02, p. 92710, §
1)
13-196-032
Maintenance of exterior walls and enclosures Application.
Exterior walls and enclosures and parts thereof of
buildings that are 80 feet or more in height above grade,
shall comply with Sections 13-196-033 to 13-196-036.
(Added Coun. J.
7-31-02, p. 91358, § 1; Amend Coun. J. 9-4-02, p. 92714, §
1)
13-196-033
Maintenance of exterior walls and enclosures Maintenance
and reporting required.*
It shall be the owner/agents duty to maintain the
buildings exterior walls and enclosures in a safe condition
and to provide periodic reports to the commissioner of
buildings. In furtherance of that requirement:
(a) the owner/agent shall: 1) arrange
for periodic critical examinations at four year intervals or
at longer intervals otherwise designated in rules and
regulations promulgated by the commissioner of buildings
pursuant to 13-196-038.5 and 2) establish an ongoing
inspection and repair program at two year intervals for each
of the intervening years.
(b) The owner/agent of buildings
constructed substantially of brick, shall: (1) arrange for
periodic critical examinations at four year intervals, or at
longer intervals otherwise established by the commissioner,
of the ornamental pieces and the parapet wall; (2) arrange
for critical examinations at four year intervals or at
longer intervals otherwise established by the commissioner,
of the lentils, which may be satisfied by scaffolding
utilizing one drop per elevation; and (3) establish an
ongoing inspection and repair program at two year intervals
for the remainder of the exterior walls and enclosures of
the building during the intervening years.
When the report indicates that repair or remedial work is
necessary, the report shall include a proposed schedule for
completion of such work.
(Added Coun. J.
7-31-02, p. 91358, § 1; Amend Coun. J. 9-4-02, p. 92710, §
1)
13-196-034
Maintenance of exterior walls and enclosures Critical
examination program.*
(a) The initial critical examination
shall be submitted for all buildings constructed prior to
January 1, 1950, by December 1, 2003, and on all buildings
constructed on or after January 1, 1950, by December 1,
2004. The initial critical examination for newly constructed
buildings shall be submitted no later than December 1 of the
fourth year following completion of the construction.
(b) Following the initial critical
examination, the exterior walls and enclosures and parts
thereof on all buildings shall be subsequently critically
examined and a report submitted at least once every four
years no later than November 1 of the fourth year following
the previous examination unless otherwise designated in
rules and regulations promulgated by the commissioner of
buildings pursuant to Section 13-196-038.5 of this code. Any
building which cannot be categorized according to the
information contained in a previously submitted critical
examination report shall be required to supplement such
report with a certification by a professional as to which
category the building belongs.
(c) The critical examination shall
include a review of all previous reports.
(d) The professional shall prepare a
report in writing on the critical examination, describing
the condition of the exterior walls and enclosures on the
building and including a record of the components and
cladding including, without limitation, any broken glass and
loose or missing glazing components; loose masonry,
concrete, EIFS, metal, stone or terra cotta; and all
significant deterioration and displacement observed.
Additionally, the report shall indicate any imminently
dangerous conditions. If any remedial work is recommended
the report shall indicate the nature and urgency of such
work.
(Added Coun. J.
7-31-02, p. 91358, § 1; Amend Coun. J. 9-4-02, p. 92710, §
1)
13-196-035
Ongoing inspection and repair program.*
(a) The ongoing inspection and repair
program shall provide inspection, reporting and preventive
maintenance of the exterior walls and enclosures and parts
thereof.
(b) No later than November 1 of every
other calendar year, the professional employed by the
owner/agent shall prepare a report in writing on the ongoing
inspection and repair program, describing the condition of
the exterior walls and enclosures and parts thereof on the
building and on any inspections, surveys or repair work
performed or to be performed on the exterior walls and
enclosures.
(Amend Coun. J.
7-31-02, p. 91358, § 1)
13-196-036
Maintenance of exterior walls and enclosures Unsafe
exterior walls and enclosures.
Every exterior wall and enclosure and parts thereof found
to be in an unsafe condition shall be subject to notice by
the commissioner of buildings to the owner/agent to take
appropriate precautionary measures and effect such repairs
or reinforcements in a timely manner as will bring the
building exterior walls and enclosures and parts thereof
into a safe condition. The owner/agent of any building which
constitutes an imminent danger and hazard to the public
shall take immediate action to have a critical examination
performed upon such building and provide the ensuing report
to the department of buildings. Additionally, the
owner/agent shall promptly begin and complete the removal,
reinforcement and/or permanent repairs necessary to make the
premises conform to the building provisions of this code,
and provide structurally safe conditions. Any costs incurred
by any department of the city in taking emergency actions
due to the dangerous and hazardous condition of an unsafe
exterior wall, including, but not limited to: closure of
vehicular traffic in a public street, rerouting of
pedestrian traffic on a public sidewalk; erection or
installation of partitions, canopies, sidewalk sheds,
barricades, scaffolding or netting, shall be a debt due and
owing to the city and recoverable from the owner/agent of
such building.
(Added Coun. J.
7-31-02, p. 91358, § 1)
13-196-036.5
Maintenance of exterior walls and enclosures Reports to
the commissioner.
The owner/agent shall submit to the commissioner of
buildings two copies of the report required under Section
12-196-034 or 12-196-035. The report shall bear the
professionals seal and signature. If acceptable, one copy
of the report shall be returned to the owner/agent, bearing
a stamp indicating acceptance by the commissioner of
buildings. The owner/agent shall maintain such reports in a
permanent building file for future reference. The fee for
examination of reports shall be $10.00 per report. However,
reports requiring extensive review of technical information
by licensed professionals within the department of buildings
shall be examined for a fee of $200.00. All reports shall
identify any persons or entities involved in the preparation
of completion of the examination and report under both the
critical examination program and the ongoing inspection and
repair program. All reports shall also include as exhibits
or attachments any and all documents, notes, summaries,
memoranda, letters or ancillary reports submitted by the
professional to the owner of buildings subject to these
requirements
(Added Coun. J.
1-1-96, p. 14639; Amend. 8-30-00, p. 39656)
13-196-038 Fines
and penalties.
Any violation of or interference with the enforcement of
any provision of Section 13-196-031 through and including
Section 13-196-037, and of Sections 13-196-204 through and
including 13-196-209, shall be punishable by a fine of not
less than $500.00 and not more than $1,000.00 for each
offense. Each day that a violation continues shall
constitute a separate and distinct offense for which a fine
as herein provided shall be imposed.
(Added Coun. J.
7-31-02, p. 91358, § 1; Amend Coun. J. 12-15-04, p. 39962, §
10)
13-196-032 Maintenance of
exterior walls and enclosures Application.
Exterior walls and enclosures and parts thereof of
buildings that are 80 feet or more in height above grade,
shall comply with Sections 13-196-033 to 13-196-036.
13-196-033 Maintenance of
exterior walls and enclosures Maintenance and reporting
required.
It shall be the owner / agents duty to maintain the
buildings exterior walls and enclosures in a safe condition
and to provide periodic reports to the commissioner of
buildings. In furtherance of that requirement:
(a) The owner / agent shall: (1) arrange
for periodic critical examinations at four year intervals or
at longer intervals otherwise established by the
commissioner and (2) establish an ongoing inspection and
repair program at two year intervals during the intervening
years.
(b) The owner / agent of buildings
constructed substantially of brick, shall: (1) arrange for
periodic critical examinations at four year intervals, or at
longer intervals otherwise established by the commissioner,
of the ornamental pieces and the parapet wall; (2) arrange
for critical examinations at four year intervals, or at
longer intervals otherwise established by the commissioner,
of the lentils, which may be satisfied by scaffolding
utilizing one drop per elevation; and (3) establish an
ongoing inspection and repair program at two year intervals
for the remainder of the exterior walls and enclosures of
the building during the intervening years.
When the report indicates that repair or remedial work is
necessary, the report shall include a proposed schedule for
completion of such work.
13-196-034 Maintenance of
exterior walls and enclosures Critical examination
program.
(a) The initial critical examination
shall be submitted for all buildings constructed prior to
January 1, 1950, by November 1, 2003, and on all buildings
constructed on or after January 1, 1950 by December 31,
2004.
(b) Following the initial critical
examination, the exterior walls and enclosures and parts
thereof on all buildings shall be subsequently critically
examined and a report submitted at least once every four
years no later than November 1 of the fourth year following
the previous examination unless otherwise extended by the
commissioner of buildings pursuant to Section 13-196-033 of
this code.
(c) The critical examination shall
include a review of all previous reports.
(d) The professional shall prepare a
report in writing on the critical examination, describing
the condition of the exterior walls and enclosures on the
building and including a record of the components and
cladding including, without limitation, any broken glass and
loose or missing glazing components; loose masonry,
concrete, EIFS, metal, stone or terra cotta; and all
significant deterioration and displacement observed.
Additionally, the report shall indicate any imminently
dangerous conditions. If any remedial work is recommended
the report shall indicate the nature and urgency of such
work.
13-196-035 Maintenance and
reporting required.
It shall be the owner / agents duty to maintain the
buildings exterior walls and enclosures in a safe condition
and provide periodic reports to the commissioner of
buildings. In furtherance of that requirement, the owner /
agent shall: 1) arrange for periodic critical examinations
at four intervals and 2) establish an ongoing inspection and
repair program at two year intervals for each of the
intervening years. When the report indicates that repair or
remedial work is necessary, the report shall include a
proposed schedule for completion of such work. Provided,
however, that the due date for the next critical examination
may be extended by the commissioner of buildings for a
period not longer than three years based upon the extent and
durability of such repairs.
13-196-036 Maintenance of
exterior walls and enclosures Unsafe exterior walls and
enclosures.
(a) Every exterior wall and enclosure
and parts thereof found to be in a unsafe condition shall be
subject to notice by the commissioner of buildings to the
owner / agent to take appropriate precautionary measures and
effect such repairs or reinforcements in a timely manner as
will bring the building exterior walls and enclosures and
parts thereof into a safe condition. The owner / agent of
any building which constitutes an imminent danger and hazard
to the public shall take immediate action to have a critical
examination performed upon such building and provide the
ensuing report to the department of buildings. Additionally,
the owner / agent shall promptly begin and complete the
removal, reinforcement and / or permanent repairs necessary
to make the premises conform to the building provisions of
this code, and provide structurally safe conditions. Any
costs incurred by any department of the city in taking
emergency actions due to the dangerous and hazardous
condition of an unsafe exterior wall, including, but not
limited to: closure of vehicular traffic in a public street,
rerouting of pedestrian traffic on a public sidewalk;
erection or installation of partitions, canopies, sidewalk
sheds, barricades, scaffolding or netting, shall be a debt
due and owing to the city and recoverable from the owner /
agent of such building.
13-196-037 Ongoing inspection and
repair program.
(a) The ongoing inspection and repair
program shall provide inspection, reporting and preventive
maintenance of the exterior walls and enclosures and parts
thereof.
(b) No later than November 1 of every
other calendar year, the professional employed by owner /
agent shall prepare a report in writing of the ongoing
inspection and repair program, describing the condition of
the exterior walls and enclosures and parts thereof on the
building and on any inspections, surveys or repair work
performed or to be performed on the exterior walls and
enclosures.
13-196-038 Fines and penalties
Any violation of or interference with the enforcement of
any provisions of Section 13-196-031 through and including
Section 13-196-037 shall be punishable by fine of not less
than $500.00 and not more than $1,000.00. Each day that such
violation shall continue shall constitute a separate and
distinct offense for which a fine as herein provided shall
be imposed.
13-196-038.5
Rules and regulations.
The commissioner of buildings may issue rules and
regulations for the administration and enforcement of the
minimum requirements for maintenance of exterior walls and
enclosures. Any person violating such rules and regulations
shall be subject to the fines prescribed in Section
12-196-039.
(Added Coun. J.
8-30-00, p. 39656)
13-196-040 Floor
loading.
Every existing building shall be so constructed and
maintained as to support safely the loads prescribed in
Chapter 13-52 of this Code, except that in building of
mercantile, industrial or storage occupancies the department
of construction and permits and fire commissioner may permit
occupancy of buildings having lower load-bearing capacity,
when satisfied that such capacity will not be exceeded by
the specific occupant. Such approved floor loads shall be
posted as required in Section 13-52-190.
In buildings where the safe load-bearing capacity is in
doubt, owing to deterioration of materials or other reasons,
the building commissioner and fire commissioner shall
require load tests to determine the safe bearing capacity.
Such load tests shall comply with the requirements of
Section 13-120-110.
(Prior code § 78-4;
Amend Coun. J. 9-13-89, p. 4604; Amend Coun. J. 6-14-95, p.
2841; Amend Coun. J. 3-5-03, p. 104990, § 39)
13-196-050 Exit
requirements.
Existing buildings shall comply with all applicable exit
requirements of this Code and with the special provisions of
Sections 13-196-060 to 13-196-090, inclusive.
(Prior code § 78-5)
13-196-060 Exits
Generally.
In existing buildings where exits do not comply with the
requirements of Chapter 13-160 and in which hazardous
conditions exist because of the number, width, construction
or location of exits, the building commissioner and fire
commissioner may order additional exits to assure adequate
safety of the occupants. Every existing building shall have
not less than the minimum number of required exits, as
prescribed in Section 13-160-050.
(Prior code § 78-6;
Amend Coun. J. 9-13-89, p. 4604)
13-196-070 Exits
Types.
In pre-ordinance buildings (built before July 7, 1957), the
building commissioner and fire commissioner may approve the
following types of exits in lieu of the required means of
vertical exit prescribed in Section 13-160-030.
(a) Fire escape stairways complying with
the requirements of Section 13-160-630 may be used in lieu
of not more than 50 percent of required stairs.
(b) A balcony, having an area of not
less than 18 square feet and provided with a ladder of
noncombustible materials extending to the ground, may be
used in lieu of one of two required stairways for a dwelling
unit having a floor level not more than 15 feet above grade.
(Prior code § 78-7;
Amend Coun. J. 9-13-89, p. 4604)
13-196-080
Passageways and exits to be unobstructed.
Every hallway, corridor, stairway, exit, fire escape door,
and other means of egress, shall be kept clear and
unencumbered at all times; and every exit area shall be
adequately lighted by electricity, in accordance with
Sections 13-160-660 and 13-160-670 of this Code.
(Prior code § 78-8)
13-196-084
Stairwell re-entry in existing buildings.
(a) In buildings not required to comply
with Chapter 13-76, every stairwell enclosure that serves
more than four stories shall comply with one of the
following requirements, as a minimum standard:
Option
1.
The stairwell enclosure doors shall not be locked from the
stairwell side at any time, in order to provide re-entry
from the stair enclosure to the interior of the building; or
Option
2.
The stairwell enclosure doors shall be equipped with a
fail-safe electronic lock release system that is activated
both manually, by a single switch accessible to building
management and firefighting personnel, and automatically,
either by approved smoke detectors or sprinkler waterflow
devices, connected to an annunciator panel. If this option
is selected, a telephone or other two-way communications
system connected to an approved station shall be provided at
not less than every fifth floor in each stairway where the
doors to the stairway are locked, no later than January 1,
2005.
During the time necessary to install a lock release system
under this Option 2, but in no event beyond December 31,
2004, the transitional measures listed as (A) through (E)
below may be used. Doors on stair enclosures may be equipped
with hardware that prevents re-entry into the interior of
the building, provided that all of the following criteria
are met:
(A) there shall be not less than two
levels where doors leading to the building interior are
permanently unlocked, permitting access to another exit
stair; and
(B) there shall be not more than four
stories intervening between stairwell enclosure doors that
provide access to another exit stair; and
(C) re-entry to the building interior
shall be possible at all times on the highest story or the
second highest story, whichever allows access to another
exit stair; and
(D) doors allowing re-entry shall be
identified as such on the stair side of the door; and
(E) doors not allowing re-entry shall be
provided with a sign on the stair side indicating the
location of the nearest door, in each direction of travel,
that allows re-entry or exit.
(b) Regardless of which option is
selected under subsection (a) of this section, stairwell
enclosure doors at the main egress level of the building
shall remain unlocked from the stairwell enclosure side at
all times.
(c) Every building of more than four
stories, and having a height in excess of 80 feet above
grade, shall comply with subsection (a) of this section upon
this sections taking effect. Every building of more than
four stories, and having a height not exceeding 80 feet
above grade, shall comply with subsection (a) of this
section no later than January 1, 2005.
(d) No later than May 1, 2004, the
executive director of the department of construction and
permits and the fire commissioner shall issue guidelines for
the approval of stations in buildings where Option 2
described in subsection (a) has been selected.
(e) Nothing in this section applies to
any stairwell enclosure door which opens directly into a
dwelling unit, provided the dwelling unit door has a
self-closer, a latch, and no self-locking hardware. Where
all doors in the stairwell meet these criteria, the
stairwell shall be provided with either a two-way
communication system as required by Option 2 above, or the
stairwell shall be provided with readily operable windows
that are operable according to ANSI A117.1-1998, Section 309
Operable Parts, on each landing or intermediate landing, no
later than January 1, 2005.
(Added Coun. J.
11-19-03, p. 14365, § 1; Amend Coun. J. 12-17-03, p.
15806, § 1)
13-196-085
Stairwell identification.
Within every building which exceeds three stories in height
there shall be posted and maintained, within every interior
stairwell enclosure at every floor, adjacent to the
stairwell door, alphabetical or directional letter
identification for the stairwell and the number of the floor
to which the door opens. Lettering shall be permanent, a
minimum of six inches in height and comply with A.D.A.A.G.
(Americans with Disabilities Act Accessibility Guidelines)
4.30.1 General, 4.30.4 Raised and Braille Characters and
Pictorial Symbol Signs, 4.30.5 Finish and Contrast, and
4.30.6 Mounting Location and Height.
Adjacent to every stairwell door there shall be posted, on
the occupancy side, information showing which floors have
re-entry locations. Lettering shall be permanent and comply
with A.D.A.A.G. 4.30.1 General, 4.30.4 Raised and Braille
Characters and Pictorial Symbol Signs, 4.30.5 Finish and
Contrast, and 4.30.6 Mounting Location and Height.
(Added Coun. J.
10-31-01, p. 71183, § 3; Amend Coun. J. 5-1-02, p. 84027, §
2)
13-196-086 Area
of rescue assistance identification.
Each area of rescue assistance shall be identified by a
sign which states area of rescue assistance and displays
the international symbol of accessibility. Lettering shall
be permanent and comply with A.D.A.A.G. 4.30 (Americans with
Disabilities Act Accessibility Guidelines).
(Added Coun. J.
10-31-01, p. 71183, § 3; Amend Coun. J. 5-1-02, p. 84027, §
1)
13-196-090 Exit,
stairway, fire escape and directional signs.
Exit, stairway, fire escape and directional signs shall be
properly installed and maintained, in accordance with
Sections 13-160-700 to 13-160-750 of this Code.
(Prior code § 78-9)
13-196-100 Smoke
detectors Where required.
All existing dwelling units as defined in Sections
13-56-020 through 13-56-040, inclusive shall be equipped
with approved smoke detectors in accordance with the
provisions of Chapter 13-196, Sections 13-196-110 through
and including 13-196-160.
(Prior code § 78-10;
Amend Coun. J. 4-15-84, p. 6189; Amend Coun. J. 6-14-95, p.
2841)
13-196-110 Smoke
detectors Installation near sleeping rooms and in living
levels.
Every owner, manager or agent of any building, as described
in Section 13-196-100, shall install, in every dwelling
unit, not less than one approved smoke detector on the
uppermost ceiling, not less than four inches from any wall,
or on a wall, located from 12 inches from the ceiling, and
within 15 feet of all rooms used for sleeping purposes, with
not less than one detector per living level containing a
habitable room or unenclosed heating plant.
(Prior code § 78-11;
Amend Coun. J. 4-25-84, p. 6189; Amend Coun. J. 9-8-86, p.
33588)
13-196-120 Smoke
detectors Interior stairwell installation.
Every owner, manager or agent of any building of Type II,
III or IV construction as described in Section 13-196-100,
shall install not less than one approved smoke detector on
the uppermost ceiling, not less than four inches from any
wall, or on a wall, located from four to 12 inches from the
uppermost ceiling of all interior stairwells.
(Prior code § 78-12;
Amend Coun. J. 9-8-86, p. 33588)
13-196-130 Smoke
detectors Standards.
All approved single station smoke detectors required in
this chapter shall be the ionization or photoelectric type,
either battery powered or 110 volt AC and shall comply with
Title 14 of the municipal code of Chicago. Smoke detectors
shall bear the label of a nationally recognized standards
testing laboratory that indicates that the smoke detectors
have been tested and listed as single or single and multiple
station smoke detectors.
In buildings required to have a standard fire alarm system
as specified in Chapter 13-196 and hotel buildings of Type
II, III or IV construction complying with Section 13-196-210
smoke detectors in dwelling units shall be of the type
tested and listed for fire protection signaling systems and
shall have an integral audible device.
(Prior code § 78-13;
Amend Coun. J. 4-25-84, p. 6189; Amend Coun. J. 9-8-86, p.
33588)
13-196-140 Smoke
detectors Owner/tenant responsibilities.
The owner shall be responsible for testing and maintaining
detectors in common stairwells. It shall be the
responsibility of the tenant to provide and maintain
functional batteries for each detector; test and maintain
detectors within dwelling units and to notify the owner or
authorized agent in writing of any deficiencies. The owner
shall be responsible for providing each tenant with written
information regarding detector testing and maintenance.
(Prior code § 78-14;
Amend Coun. J. 4-25-84, p. 6189)
13-196-150 Smoke
detectors Unlawful acts.
It shall be unlawful for any person to remove batteries or
in any way make inoperable smoke detectors as provided for
in this chapter.
(Prior code § 78-15)
13-196-160 Smoke
detectors Multifamily and single-family installation
When.
Smoke detectors required by this law shall be installed
within three months in all multiple dwellings as defined in
Section 13-56-040. Smoke detectors required in single-family
dwellings as defined in Section 13-56-030 shall be installed
within six months from the date of passage of this
ordinance.
(Prior code §
78-15.1; Added Coun. J. 4-25-84, p. 6189; Amend Coun. J.
6-14-95, p. 2841)
13-196-165 Carbon
monoxide detectors.
All existing buildings shall comply with all applicable
requirements in Chapters 13-64 and 18-28 of this Code for
the installation and maintenance of carbon monoxide
detectors.
(Added Coun. J.
3-14-07, p. 99609, § 2)
13-196-170
Self-closing devices required for corridor doors.
In residential buildings exceeding four stories in height,
all apartment doors opening upon public corridors shall be
equipped with approved self-closing devices. In all new and
existing single-room occupancy buildings, irrespective of
height, all dwelling unit doors opening to public corridors
shall be equipped with approved self-closing devices.
(Prior code § 78-16;
Amend Coun. J. 5-4-94, p. 49750)
13-196-180
Sprinkler systems Where required.
The following existing buildings or structures, or parts
thereof, are to be equipped with sprinkler systems complying
with the requirements of Chapter 15-16:
(a) Every building of construction Type
III or IV and of two stories or more in height, used in part
or in whole as a Type I school, hospital, infirmary,
nursery, orphanage, sheltered-care home, sanitoria or home
for the aged or used in whole as a Type II school;
(b) Every building used in whole or in
part as a mens cubicle hotel which does not comply with
Section 13-64-020(a) of this Code;
(c) Every building used primarily as an
exhibition area or in that portion of any building used as
an exhibition area;
(d) Every building used in whole or in
part as a nursing home, as defined, in Chapter 4-96 of this
Code;
(e) Areas used for storage of
combustible containers in new and existing buildings, with
exhibition areas, shall be enclosed with a two-hour fire
resistive construction, and shall be equipped with a
standard sprinkler system, as defined in Chapter 15-16 of
this Code.
(Prior code § 78-17)
13-196-190
Standpipe systems Where required.
Standard inside standpipe systems, complying with the
requirements of Chapter 15-16, shall be provided in all
buildings exceeding 80 feet in height with the following
exceptions:
(a) Institutional Units. In
institutional units, standpipes shall be provided in all
buildings more than four stories or 55 feet in height.
(b) Stage Blocks. In stage
blocks, standpipes shall be provided on each side of the
stage, on each tier of dressing rooms, and within 55 feet of
all property rooms, store rooms or work rooms.
(c) Storage Structures.
Standpipes shall not be required in grain elevators or
similar storage structures, where such standpipes are
ineffective owing to the type of structure and
inaccessibility of hose connections.
For the purpose of determining standpipe requirements, the
height of a building shall be determined in accordance with
the provisions of Section 13-48-020. Towers, steeples, tanks
and similar structures not intended or used for human
occupancy shall not be considered in determining the height.
(d) This section shall not apply to a
building used as a business unit or storage unit, in
existence prior to January 20, 1950, which is equipped
throughout with an approved system of automatic sprinklers
or is a fire resistive building of Type IA, IB or IC
construction, provided that a standpipe system complying
with Section 15-16-1190 is also provided in the building.
(e) In exhibition areas standpipes shall
be provided regardless of the height of the building and
standpipe locations shall provide complete coverage of the
fire area with 100 foot hose lengths and 30 foot hose
streams.
(Prior code § 78-18)
13-196-200
Standard fire alarm system requirements.
An approved fire alarm system shall be provided as required
in this section.
(a) A standard fire alarm system meeting
the requirements of this chapter and Chapter 15-16 of this
Code shall be provided in the following occupancies:
(1) Institutional:
Buildings two stories or less in height with a floor area
which does not exceed 8,000 square feet shall be equipped
with a Class I system. Buildings over two stories in height
or with a floor area exceeding 8,000 square feet shall be
equipped with a Class II system;
(2) Type I or Type II schools:
Buildings over one story in height shall be equipped with a
Class I system;
Any Type I school operating as or containing a day care
center Class I, as defined in Chapter 4-72, shall comply
with fire alarm system requirements applicable to Type III
schools;
(3) Type III schools: Class I
system;
(4) Hotels:
Buildings of Types II, III or IV construction 80 feet or
less in height shall be equipped with a Class I system
except where 25 or fewer persons sleep above the second
floor;
(5) Single-room occupancy buildings:
new and existing single-room occupancy buildings two stories
or more in height, which are not equipped with a complete
automatic sprinkler system, shall be equipped with a Class I
fire alarm. The approved standard Class I control equipment
may use microprocessor based program-controlled
communication circuits when the control equipment is of a
type tested and conforming to Underwriters Laboratories
standard 864-1991 for the intended use. The stored program
(software) installed figuration for such systems shall be
incapable of change, except that a manufacturers authorized
technician may make changes for proper system operation when
such changes are approved by the deputy commissioner of the
fire prevention bureau. Any changes, repairs or maintenance
on such systems shall be performed only by or under the
direction of a licensed supervising electrician.
(6) Dormitories:
Buildings two stories or more in height; except those where
25 or fewer persons sleep above the second floor, shall be
equipped with a Class I system;
(7) Intermediate care facilities for the
developmentally disabled 15 or fewer persons, same as
institutional uses.
(b) Hotels:
Buildings of Type 1 construction over four stories but not
over 80 feet in height shall be equipped with an approved
fire alarm system including smoke detectors, heat detectors
and water flow alarm devices installed in accordance with
NFPA 72A-1985 and annunciated visually and audibly for each
individual floor at a fire panel located near a main
entrance to the building. A one-way voice communication
system controlled from the fire panel location and meeting
the requirements of Section 13-196-210(e)(2) of this Code
shall be provided. Use of the one-way voice communication
system in a fire emergency by other than department of fire
personnel shall be prohibited.
(1) The fire alarm system shall be zoned
horizontally based on the system design, but in no case
shall there be less than one zone per floor.
(2) The fire alarm system shall be
monitored by an Underwriters Laboratories Inc. listed
Central Station service or shall be a Proprietary Protective
Signalling System (installed in accordance with National
Fire Protection Association Standard NFPA 72D-1986).
(3) A fire panel consisting of fire
alarm controls, annunciator panel, and one-way voice
communications system controls shall be provided in a
location approved by the bureau of fire prevention. Fire
panels installed prior to the passage of this ordinance
located on grade level in a readily accessible location
shall be accepted.
(4) Plans for all systems to be
installed shall be submitted to the bureau of fire
prevention for approval and systems used shall meet the
approval of the fire prevention bureau.
(c) Notwithstanding any other provision
of this Code to the contrary, the revisions to the
requirements of this chapter and Chapter 15-16 contained in
this amendatory ordinance shall apply to schools and day
care centers in existence on the effective date of this
amendatory ordinance beginning July 1, 1991.
(d) The requirements of subsection
(a)(5) of this section shall be enforced against all
single-room occupancy buildings effective June 30, 1995. All
existing single-room occupancy buildings which will require
installation of a Class I alarm system shall submit plans to
the fire prevention bureau for approval of such system on or
before January 1, 1995.
(Prior code § 78-19;
Amend Coun. J. 9-8-86, p. 33588; Amend Coun. J. 6-27-90, p.
17613; Amend Coun. J. 5-4-94, p. 49750)
13-196-203 Life
safety data sheet Required.
(A) No later than April 1, 2005, any
owner of an existing building exceeding 80 feet in height
above grade shall file with the fire department a life
safety data sheet containing the following information about
the building; (1) the name of the building owner of record,
and, if applicable, the building manager; (2) the address of
the building; (3) whether the building is residential or
commercial or of mixed use; (4) if the building is
residential or of mixed use, the number of dwelling units in
the building; (5) the number of stories in the building; (6)
whether the building is equipped with an automatic sprinkler
system meeting any or all of the requirements of Chapter
15-16 of this Code, and identifying the areas so protected;
and (7) whether the building is equipped with a standard
inside standpipe system, a fire pump and a smokeproof tower.
(B) All information contained in the
life safety data sheet shall be kept current. Any change in
required information shall be reported by the building owner
to the fire department within 14 days after the change. This
subsection shall be enforceable against the building owner
and against any subsequent owner.
Any person who violates the requirements of this section
shall be fined not less than $200.00 nor more than $500.00
for each offense. Each day that a violation continues shall
constitute a separate and distinct offense.
(Added Coun. J.
12-15-04, p. 39962, § 1)
13-196-204 Voice
communication systems in existing buildings.
(A) Subject to the exceptions listed
below, no later than January 1, 2012, every existing
building exceeding 80 feet in height above grade shall be
equipped with the following: (i) a one-way voice
communication system meeting the requirements of Section
13-76-050(b); and (ii) a two-way voice communication system
meeting the requirements of Section 13-76-050(a); provided,
however, that a telephone or other two-way communication
system connected to an approved station, and installed
pursuant to and in accordance with Option 2 of Section
13-196-084(a), shall be deemed to satisfy the requirements
of item (ii) of this subsection.
(B) Neither a one-way nor a two-way
voice communication system shall be required in the
following buildings:
Exception
Number 1: Buildings that are classified as Class A-2,
Multiple Dwellings, and are for non- transient residential
use and are fully protected by automatic sprinklers.
Exception
Number 2: Institutional buildings and schools that have
an approved standard fire alarm system as required by
Section 15-16-110.
(C) A one-way voice communication system
shall not be required in the following buildings:
Exception
Number 1: Non-transient residential buildings with an
existing occupant notification system if a detailed
description of the existing occupant notification system is
submitted to and approved by the commissioner of buildings
and the fire commissioner or by their designated
representatives. In order to be considered for approval
under this exception, and if approved under this exception,
the existing occupant notification system shall meet the
following criteria:
(a) the system must be in continuous use
and must be tested on a monthly basis, or the system must
have electronic supervision to indicate operational
deficiencies in the system including, but not limited to,
shorts, grounds and breaks in the circuit wiring; and
(b) the system must be audible
throughout all required areas of the building, or must
produce within all dwelling units a minimum sound level of
45 dBA within ten feet of any existing occupant notification
system device; and
(c) the system must be able to transmit
voice instructions without delay; and
(d) the system must be able to transmit
voice instructions to all required areas or to all dwelling
units at the same time; and
(e) the system must be available for
fire department use from a central command location; and
(f) the system is subject to field
testing; and
(g) replacement or modification of
system components to meet the above criteria is limited to
50 percent of the reproduction cost of the existing occupant
notification system.
(D) A two-way voice communication system
shall not be required in the following buildings:
Exception
1:
Buildings that are classified as Class A-2, Multiple
Dwellings, and are for non-transient residential use if the
building does not exceed 15 stories in height and contains
60 or fewer dwelling units as defined in Section 13-4-010.
(E) For purposes of this
section, non-transient residential means a residential use
other than a hotel, motel, bed-and-breakfast establishment,
dormitory, transitional shelter, emergency shelter or other
temporary residential use.
(F) This section shall be enforceable
against the building owner and against any subsequent owner.
(Added Coun. J.
12-15-04, p. 39962, § 2)
13-196-205
Automatic sprinkler system installation in existing
high-rise buildings.
Subject to the exceptions listed below, every existing
building exceeding 80 feet in height above grade shall be
protected throughout by an approved automatic sprinkler
system meeting the requirements of Chapter 15-16 of this
Code unless otherwise provided by Section 13-196-207. The
owner of each such building shall, no later than September
1, 2005, submit for approval to the bureau of fire
prevention a plan for compliance with the requirements of
this section. The requirements of this section shall be
enforceable against the building owner and against any
subsequent owner.
Every building subject to the provisions of this section
shall comply with the following schedule for installation of
an approved automatic sprinkler system: one-third of the
gross square footage of the building shall be equipped with
automatic sprinklers by January 1, 2009; two-thirds of the
gross square footage of the building shall be equipped with
automatic sprinklers by January 1, 2013; and the entire
gross square footage of the building shall be equipped with
automatic sprinklers by January 1, 2017. Buildings subject
to any of the following exceptions 3 through 7, inclusive,
shall comply with the requirements of Section 13-196-206.
Exception
Number 1: An open-air parking facility meeting the
requirements of Section 13-96-920 of this Code.
Exception
Number 2: The open-air portions of a stadium.
Exception
Number 3: A building that is classified as a Class A-2,
Multiple Dwelling, and that is a non- transient residential
use. This exception includes (a) all approved auxiliary use
areas of the building other than parking garages; and (b)
any parking garage in the building that is used exclusively
by the buildings non- transient residential occupants and
their guests or by persons who, pursuant to a written lease
agreement, rent space in the buildings parking garage for
use by a designated motor vehicle in time increments of at
least one month in duration.
Exception
Number 4: The following portions of a building
classified as a mixed occupancy building:
(A) any portion of a mixed occupancy
building that is classified as a Class A-2, non-transient
residential use;
(B) any approved auxiliary use area
wholly contained within a Class A-2, non-transient
residential use portion of a mixed occupancy building;
(C) any parking garage in a mixed
occupancy building that is used exclusively by the
buildings non- transient residential occupants and their
guests or by persons who, pursuant to a written lease
agreement, rent space in the buildings parking garage for
use by a designated motor vehicle in time increments of at
least one month in duration;
(D) any portion of a mixed occupancy
building, other than those portions of the building
classified as a Class A-2, non-transient residential use, if
all of the following criteria are met:
(1) the cumulative total of the
buildings floor areas not classified as a Class A-2,
non-transient residential use does not exceed ten percent of
the total floor area of the building. The floor areas of
parking garages used exclusively by the buildings
non-transient residential occupants and their guests shall
be excluded from the calculation of the buildings total
floor areas not classified as a Class A-2, non-transient
residential use and from the calculation of the total floor
area of the building; and
(2) occupancy separations are provided
in accordance with Table 13-56-280 as set out in Section
13-56-280 of this Code; and
(3) the mixed occupancy building must be
either of Type I, fire-resistive construction or of Type II,
non-combustible construction; and
(4) all of the exempted areas within the
mixed occupancy building, other than those portions of the
building classified as a Class A-2, non-transient
residential use, are located in the building at a floor
level elevation that does not exceed 80 feet in height above
average grade.
Exception
Number 5: A building designated as a Chicago Landmark
pursuant to Article XVII of Chapter 2-120 of this Code
unless the landmarked building is required to be equipped
with an automatic sprinkler system by other provisions of
this Code.
Exception
Number 6: A building within a landmark district
designated pursuant to Article XVII of Chapter 2-120 of this
Code and determined to be a contributing building unless the
contributing building is required to be equipped with an
automatic sprinkler system by other provisions of this Code.
Exception
Number 7: A building color-coded red or orange in the
Chicago Historic Resources Survey, published in 1996,
unless the building is required to be equipped with an
automatic sprinkler system by other provisions of this Code.
For purposes of this section, non-transient residential
means a residential use other than a hotel, motel,
bed-and-breakfast establishment, dormitory, transitional
shelter, emergency shelter or other temporary residential
use.
(Added Coun. J.
12-15-04, p. 39962, § 3)
13-196-206 Life
safety evaluation of existing high- rise buildings.
(A) No later than January 1, 2005, the
commissioner of buildings shall adopt by rule and publish
criteria for life safety evaluations of all existing
buildings exceeding 80 feet in height above grade that are
not required by Section 13-196-205 to be protected
throughout by an approved automatic sprinkler system. The
criteria adopted pursuant to this subsection shall provide
sufficient protection to life and safety of building
occupants. The criteria shall be developed based on a review
of available resources, including standardized building and
safety codes and the practices of other municipalities.
(B) The owner of any building qualifying
for any exception 3 through 7, inclusive, of Section
13-196-205 shall have the building evaluated for life safety
by a licensed professional engineer or by a licensed
architect; provided, however, that this requirement shall
not apply to any building which is protected throughout by a
previously approved automatic sprinkler system. The licensed
engineer or architect shall prepare a life safety evaluation
of the building in accordance with the requirements of this
section and with any rules and regulations promulgated
thereunder. The life safety evaluation shall be signed and
sealed by the person who prepared it and shall contain an
explicit statement acknowledging that the information
contained therein is true and complete.
(C) If, based on the use of a scoring
system described by rule to conduct the life safety
evaluation, the licensed professional engineer or licensed
architect determines that the building achieves the minimum
score required on the life safety evaluation, the licensed
engineer or architect shall certify the evaluation as a life
safety compliance plan and shall give the life safety
compliance plan to the building owner. No later than January
1, 2006, the building owner shall submit the life safety
compliance plan to the department of buildings and the
bureau of fire prevention. The life safety compliance plan
shall be enforceable against the building owner and against
any subsequent owner.
(D) If, based on the use of a scoring
system described by rule to conduct the life safety
evaluation, the licensed professional engineer or licensed
architect determines that the building does not achieve the
minimum score required on the life safety evaluation, the
building owner shall, no later than January 1, 2006, submit
the life safety evaluation to the department of buildings
and the bureau of fire prevention along with either: (1) a
proposal to protect the building throughout with an
automatic sprinkler system meeting the requirements of
Chapter 15-16 of this Code unless otherwise provided by
Section 13-196-207, notwithstanding any exceptions for which
the building may have otherwise qualified pursuant to
Section 13-196-205, and using the schedule for installation
described in Section 13-196-205; or (2) a proposal for
achieving the minimum score required on the life safety
evaluation by making specified modifications to the
building.
Any proposal submitted pursuant to this subsection shall be
signed and sealed by a licensed professional engineer or by
a licensed architect. In addition, any proposal submitted
pursuant to item (2) of this subsection shall contain (i) an
explicit statement by the licensed engineer or architect
certifying that if the modifications identified in the
proposal are fully implemented, the building will receive
the minimum score required on the life safety evaluation;
and (ii) a timetable for completion of those modifications
to be phased in over a stipulated period of years, but no
later than January 1, 2012, at which time the modifications
identified in the proposal shall be fully implemented. Any
schedule for installation or timetable required by this
subsection shall be enforceable against the building owner
and against any subsequent owner.
If, after reviewing the certified proposal, the
commissioner of buildings and the deputy commissioner of the
bureau of fire prevention determine that the certified
proposal, when fully implemented, will enable the building
to achieve the minimum score required on the life safety
evaluation, the commissioner and deputy commissioner shall
jointly accept the certified proposal as a life safety
compliance plan. The life safety compliance plan shall be
enforceable against the building owner and against any
subsequent owner.
(E) No permit shall be issued for work
on any existing building that is the subject of a life
safety compliance plan unless the licensed architect or
licensed engineer of record identified in the permit
application certifies in writing that the permitted work
will not reduce or otherwise negatively impact the score of
the life safety evaluation on which the life safety
compliance plan is based; nor shall any permit be issued for
work on a building whose owner is in violation of any of the
requirements of this section unless the permit is necessary
to cure the violation.
(F) Nothing in this section shall be
construed to waive any provision of the Municipal Code of
Chicago applicable to existing buildings or to relieve any
person from full compliance with those provisions.
(Added Coun. J.
12-15-04, p. 39962, § 4)
13-196-207
Materials and installation standards for retrofit fire
protection systems.
In every existing high-rise building subject to the
requirements of Sections 13-196-204, 13-196-205 or
13-196-206 of this Code, the following materials and
installation standards shall apply to newly installed fire
protection systems:
(A) An existing water supply that serves
an existing fire department wet standpipe system may also
serve as the water supply for retrofit sprinkler systems,
provided the water supply meets, non-simultaneously, the
larger of either the standpipe demand at the time of the
original installation, or the new sprinkler system demand
including hose stream allowance.
(B) Notwithstanding the requirements of
Sections 18-28-602.2.1 and 15-16-370, sprinkler piping and
sprinklers shall meet or exceed the requirements of NFPA
13-2002 and their respective product listings issued by an
approved independent laboratory or agency.
(C) Automatic sprinkler systems shall
meet or exceed the requirements of NFPA 13-2002 except that
at least one sprinkler shall be provided within the stairway
enclosure at the landing serving the door(s) to each floor.
(D) If repairs or minor modifications
are made to existing dry-pipe sprinkler systems, the zoning
of the system may remain as originally installed.
(E) Low-voltage electrical wiring risers
for fire detection and fire alarm notification systems may
be installed in stairways, notwithstanding the requirements
of Section 15-8-180, if the wiring is in conduit and does
not obstruct the required egress width of a stairwell.
(F) Low-voltage electrical branch wiring
in horizontal runs for voice communication systems may be
installed without conduit, unless required by other sections
of this Code, if the wiring (i) is limited combustible FHC
25/50 CMP; and (ii) has a maximum Class 1 flame spread
rating as defined in Section 15-12-040; and (iii) has a
smoke developed rating not to exceed 50 when tested in
accordance with ASTM-E 84.
(G) Low-voltage electrical wiring for
fire detection systems may be run in the same conduit as
low-voltage electrical wiring for fire alarm notification
systems, as permitted by NFPA 72-2002 and the product
listings of the wire and the conduit issued by an approved
independent laboratory or agency.
(H) Low-voltage fire detection equipment
panels and low-voltage fire alarm notification equipment
panels may be installed in the same panel box, as permitted
by NFPA 72-2002 and the products listing issued by an
approved independent laboratory or agency.
(I) Central station monitoring of fire
alarm systems may use digital alarm communicators with
constant supervision, as permitted by NFPA 72-2002.
(Added Coun. J.
12-15-04, p. 39962, § 5)
13-196-208
Smokeproof towers in existing high- rise buildings Fire
shields.
If fire shields in smokeproof towers are provided to
protect openings of balconies or vestibules in existing
buildings exceeding 80 feet in height above grade, such fire
shields shall comply with the requirements of this section.
(A) Fire shields shall comply with all
applicable requirements for fire windows as provided in
Section 15-12-160.
(B) Fire shields shall have an opening
sash having a clear area not less than as required in
Section 13-160-380(c), arranged to open automatically in
case of fire to the full limit and to be held securely in
such open position. Provision shall be made for the manual
opening or closing of the sash.
(C) The automatic opening of the sash
shall be actuated by approved devices located inside the
building within five feet of the door from the building to
the vestibule or balcony and located also on the ceiling of
the vestibule or balcony. Such devices shall be designed to
operate as a result of rate of temperature rise or when the
surrounding air reaches a temperature of 120 degrees
Fahrenheit.
(D) Each fire shield sash shall be
tested annually to verify automatic operation as required in
subsection (c) of this section. Testing shall be performed
by an individual or organization approved by the deputy
commissioner in charge of the bureau of fire prevention.
Reports of the testing shall be filed with the bureau by
June 30 of each year.
(Added Coun. J.
12-15-04, p. 39962, § 6)
13-196-209
High-rise buildings Stairways Doors Frames.
No later than January 1, 2012, doors and frames in
stairways in all existing residential buildings and
buildings of mixed residential occupancy exceeding 80 feet
in height above grade shall have a fire resistance rating of
at least one hour.
(Added Coun. J.
12-15-04, p. 39962, § 7)
13-196-210 High
rise fire systems.
Any existing or preordinance building exceeding 80 feet in
height designed or used in whole or in part as a hotel shall
be equipped with a high rise fire system as required in this
section.
(a) In buildings equipped with an
approved system of automatic sprinklers, an approved fire
alarm system including all water flow alarm devices shall be
required. Sprinklers may be omitted in guest room closets
not over 24 square feet in area. Other areas not sprinkled,
because of unreasonable hardship or as permitted by Section
15-16-350 of this Code, shall be protected by approved smoke
detectors or other fire detection measures approved by the
bureau of fire prevention. Detectors shall not be required
in guest room bathrooms. No automatic smoke detector shall
be required in guest room corridors nor elevator lobbies of
existing buildings having automatic sprinkler systems
installed prior to the passage of this ordinance on guest
room floors except that sprinklers may be omitted in guest
room bathrooms over 55 square feet in area with
noncombustible plumbing fixtures and with walls and ceilings
surfaced with noncombustible materials.
(b) In buildings not equipped with an
approved system of automatic sprinklers an approved fire
alarm system, including smoke detectors, heat detectors and
water flow alarm devices, shall be required. System devices
shall be installed as follows:
(1) As required by Section 13-196-240 of
this Code;
(2) Heat detectors shall be installed in
restaurants, meeting rooms and lounges.
(c) The fire alarm system shall be zoned
horizontally based on the system design, but in no case
shall there be less than one zone per floor.
(d) The fire alarm system shall be a
Proprietary Protective Signalling System installed in
accordance with National Fire Protection Association
Standard NFPA 72D-1986 or shall be monitored by an
Underwriters Laboratories Inc. listed Central Station
service.
(e) There shall be two voice
communication systems as follows:
(1) A two-way fire department
communications system providing emergency two-way stations
in each required stairwell at not less than every fifth
floor and at the fire panel. The system shall be zoned not
less than one zone per stairwell. Systems installed prior to
the passage of this ordinance using phone jacks zoned by
stairwell shall be accepted in lieu of two-way stations.
(2) A selecting one-way communication
system with speakers in passenger elevators, in elevator
lobbies, in stairwells at not less than every fifth floor,
and in corridors at intervals not exceeding 75 feet. Use of
the one-way voice communication system in a fire emergency
by other than department of fire personnel shall be
prohibited. Zoning of speakers shall be as follows:
passenger elevators zoned by elevator lobby; elevator
lobbies and corridors zoned horizontally based on the system
design, but in no case less than one zone per floor;
stairwells zoned vertically by stairwell. Approved elevator
speaker intercom systems installed prior to the passage of
the ordinance shall be accepted for communication to
elevators as long as the systems are maintained in good
working order.
The two-way fire department communication system may be
combined with the one-way system.
(f) A fire panel consisting of fire
alarm controls, annunciator panel, and one- and two-way
voice communications system controls shall be provided in a
location approved by the bureau of fire prevention. Fire
panels and controls installed prior to the passage of this
ordinance located on grade level in a readily accessible
location shall be accepted.
(g) Plans for systems to be installed
shall be submitted to the bureau of fire prevention for
approval and systems used shall meet the approval of the
fire prevention bureau.
(h) In buildings of Type II, III or IV
construction, an automatic central alarm shall be installed
and be audible throughout the corridors of the building and
shall be activated by the sprinkler flow alarm and smoke
detectors.
(Prior code §
78-19.1; Added Coun. J. 9-8-86, p. 33588)
13-196-220 Class
II standard fire alarm systems.
A Class II standard fire alarm system may be installed in
lieu of a Class I standard fire alarm system in any building
when, in the opinion of the division marshal in charge of
the bureau of fire prevention, the number of people involved
and the physical construction of such building makes a Class
II standard fire alarm system acceptable. Class II standard
fire alarm system shall comply with the provisions of
Chapter 15-16.
(Prior code § 78-20)
13-196-230 Floor
area and height.
In every building described in Section 13-196-200, as
requiring a standard fire alarm system, the area of such
building shall be the total area of the building and the
height shall be the total height of such building including
the space used for occupancies other than for institutional,
school, hotel, or single-room occupancies.
(Prior code § 78-21;
Amend Coun. J. 5-4-94, p. 49750)
13-196-240
Automatic fire detectors Where required.
In every fire alarm system required in this Code, automatic
fire detectors shall be installed as an integral part of a
fire alarm system in rooms or portions of the building as
follows:
(a) In all rooms where a flammable
compressed gas or flammable liquid as described in Chapters
4-112* and 15-24, other than fuel oil for heating, is stored
or used; also in shops and storerooms where combustible
material is stored or handled.
(b) In every building used in part as an
institutional building, school, hotel, or single-room
occupancy, an automatic fire detector shall be installed in
such portion or portions of the building used for purposes
other than institutional, school, hotel, or single-room
occupancy purposes, unless such institutional building,
school, hotel, or single-room occupancy is separated from
all other occupancies by a separation with a fire resistive
value as specified in Section 13-56-280. Such automatic fire
detectors shall be installed, spaced and located in
accordance with the recommendations, based upon actual
tests, prescribed by a nationally recognized testing
laboratory acceptable to the fire prevention bureau.
(c) In every storeroom, maintenance
shop, fan room, mechanical equipment room, laundry, linen
room, janitor closet, kitchen and storage area.
(d) Fire alarm systems serving Type III
schools, day care centers Class II, and those Type I schools
operating as or containing a day care center Class I as
defined in Chapter 4-72 shall include automatic detectors as
follows:
1. Smoke detectors shall be installed at
each floor level, including basements, of each interior
stairwell up to and including one level above the level of
the school or day care center, except in unoccupied attics.
2. Smoke detectors shall be installed in
front of doors to stairwells from the school or day care
center and at intervals of no less than 30 feet in all
corridors within or serving the school or day care center.
3. Smoke detectors shall be located in
all lounges, recreation areas and sleeping rooms.
4. Heat detectors shall be installed in
boiler rooms, kitchens and combustible storage areas except
where a sprinkler system with a flow alarm connected to the
fire alarm system is installed in such rooms.
(e) In all two-story buildings occupied
as open plan schools, (a story located below grade level
shall be counted, if used for other than building service
purposes), approved automatic fire detectors shall be
installed throughout the building and be interconnected to
the school fire alarm system.
(f) In hotel buildings over four
stories, electrical equipment rooms, guest room corridors
and elevator lobbies shall be equipped with automatic smoke
detectors installed in accordance with NFPA 72E-1984.
(g) In single-room occupancy buildings,
automatic heat detectors shall be installed in each
single-room occupancy unit, in public corridors, and at each
floor level in every interior stairwell. In single- room
occupancy buildings, smoke detectors required by Section
13-196-100 of this Code need not be connected to the fire
alarm system, but shall be permanently wired to the
electrical wiring system of the building.
(Prior code § 78-22;
Amend Coun. J. 9-8-86, p. 33588; Amend Coun. J. 6-27-90, p.
17613; Amend Coun. J. 5-4-94, 49750)
13-196-250
Permitted omission of sprinklers, heat and smoke detectors.
No automatic heat detector shall be required in any room or
portion of a building which is equipped with an approved
installation of automatic sprinklers and provided with a
water flow alarm which is connected to the fire alarm
system. No automatic smoke detector shall be required in
guest room corridors nor elevator lobbies of hotel buildings
equipped with an approved system of automatic sprinklers.
Sprinklers may be omitted in guest room closets not over 24
square feet in area. Other areas not sprinklered, because of
unreasonable hardship or as permitted by Section 15-16-350
of the code, shall be protected by approved smoke detectors
or other fire detection measures approved by the bureau of
fire prevention. Detectors shall not be required in guest
room bathrooms. No automatic smoke detector shall be
required in guest room corridors nor elevator to the lobbies
of existing buildings having automatic sprinkler systems
installed prior to the passage of this ordinance on guest
room floors except that sprinkler systems installed prior to
the passage of this ordinance on guest room floors except
that sprinkler systems may be omitted in guest room
bathrooms over 55 square feet in area with noncombustible
plumbing fixtures and with walls and ceilings surfaced with
noncombustible materials.
(Prior code § 78-23;
Amend Coun. J. 9-8-86, p. 33588)
13-196-260 Fire
extinguishers.
Standard fire extinguishers shall be provided in accordance
with the provisions of Sections 15-16-620 through and
including 15-16-680 of this Code.
(Prior code § 78-24)
13-196-270
Elevator recall.
All existing buildings shall comply with the requirements
of Section 18-30-2600.
(Added Coun. J.
6-14-95, p. 2820; Amend Coun. J. 1-10-01, p. 50236, § 2)
13-196-280
Reserved.
13-196-290
Pre-ordinance hotels.
Every pre-ordinance hotel (built before July 7, 1957) more
than two stories and basement in height, having sleeping
accommodations for more than 25 persons above the second
story, and every pre-ordinance hotel of any capacity more
than four stories and basement in height, shall comply with
the requirements of Section 15-8-120 pertaining to the
protection of stairs, shafts and vertical openings, except
as follows:
(a) Enclosing walls and partitions may
be of construction providing fire resistance of not less
than one hour.
(b) Doors required for protection of
openings in enclosures may be Class C fire doors of
combustible material faced on both sides with materials not
less fire resistive than sheet steel 18 gauge in thickness.
Openings, if any, shall be glazed with wire glass and shall
not exceed 144 square inches in area, except that existing
openings not exceeding 1,296 square inches in area may be
permitted.
(c) Where the top or bottom riser in a
stairwell is so located that the vertical enclosures therein
required will not be practical to erect without unreasonable
hardship, a horizontal cutoff there shall be not more than
three openings to dwelling units or other nonpublic spaces
on each floor, and such dwelling units or nonpublic spaces
shall be separated from the corridor by partitions providing
fire resistance of not less than one hour with all openings
protected with self-closing Class C fire doors.
(Prior code § 78-27)
13-196-300
Institutional units.
In every pre-ordinance institutional building, every room
used for the storage or application of anesthetics
consisting of flammable or explosive gases or mixtures,
including cyclopropane, ether chloride, ethylene, propylene,
or any flammable liquids, shall have safeguards for
installation and operation of such rooms and equipment as
follows:
(a) Any cylinders containing
anaesthetizing gases or liquids shall be plainly marked with
the name of the substance which they contain and shall
comply with the requirements of the Interstate Commerce
Commission for such containers. Such cylinders or containers
shall not be stored in any operating room. Approved
regulators or gas flow devices shall be provided for any
such substances, except low pressure oxygen containers.
No such regulators or gas flow devices shall permit the
intermixing of gases by any error or manipulation.
(b) The construction and equipment of
operating rooms shall comply with the applicable
requirements of Section 13-80-040.
(Prior code § 78-28)
13-196-310
Roominghouses.
Every roominghouse and every rooming unit shall be in
compliance with the minimum standards set forth in this
chapter, except as modified in Section 13-196-320.
(Prior code § 78-29)
13-196-320
Roominghouses Sanitary facilities.
At least one flush water closet, lavatory basin and bathtub
or shower shall be supplied for each ten persons or fraction
of ten within a roominghouse, including members of the
family of the owner if they share the use of the facilities.
All such facilities shall be properly connected to required
water and sewage systems and shall be located within the
dwelling so as to be reasonably accessible from a common
hall or passageway to all persons sharing such facilities,
and shall not be more than one story removed from the
rooming unit of any occupant intended to share the
facilities. In a roominghouse in which rooms are let only to
males, flush urinals may be substituted for not more than 33
and one-third percent of the required number of water
closets.
In a roominghouse where both sexes are accommodated, the
water closets shall be separately calculated, based on the
occupancy of each sex, except where not more than two water
closets are required.
(Prior code § 78-30)
13-196-330
Roominghouses Responsibility of operator.
Every operator of a roominghouse shall be responsible for
the following matters required by this chapter:
extermination of insects, rodents, or other pests in it or
in its yard; disposal of refuse by placing in it disposal
facilities supplied by him; hanging and removing all screens
required; sanitary maintenance of all walls, floors and
ceilings; maintenance of a sanitary condition in every part
of the roominghouse; and proper installation and repair of
every facility.
(Prior code § 78-31)
13-196-340
Minimum requirements for residential buildings General.
The provisions of these Sections 13-196-350 through and
including 13-196-640 are applicable to occupancy for
residential purposes of any building, whether or not such
building was erected, altered or converted in full or
substantial compliance with ordinances in force at the time
of its erection, alteration, or conversion and whether or
not such building was erected, altered or converted prior to
the effective date of this Code. The requirements imposed by
these sections shall be in addition to other applicable
requirements for existing buildings imposed by other
provisions of Chapter 13-196.
(Prior code § 78-32)
13-196-350
Residential buildings Water closet.
Every family unit except as provided in Section 13-196-380
shall contain within its walls, a room, separate from the
habitable rooms, which affords privacy to a person and is
equipped with a flush water closet.
(Prior code § 78-33)
13-196-360
Residential buildings Lavatory.
Every family unit except as provided in Section 13-196-380
shall contain within its walls a lavatory basin located in
the same room as the required water closet, or as near to
that room as practicable.
(Prior code § 78-34)
13-196-370
Residential buildings Bathtub or shower.
Every family unit except as provided in Section 13-196-380
shall contain within its walls a room, separate from the
habitable rooms, which affords privacy to a person in the
room and which is equipped with a bathtub or shower.
(Prior code § 78-35)
13-196-380
Residential buildings Limitations on sharing sanitary
facilities.
The occupants of not more than two-family units which are
located in the same dwelling, may share a single flush water
closet, a single lavatory basin, a single bathtub or shower
if:
(a) The facilities to be shared are
within a room or rooms on the same floor as the family units
and are accessible to the occupants of each family unit
without going through the family unit of another person or
outside the dwelling; and
(b) Neither of the two-family units
contains more than two habitable rooms nor more than 500
square feet of floor area, excluding of the number of rooms
and from floor area any kitchen of less than 70 square feet
of the floor area.
(Prior code § 78-36)
13-196-390
Residential buildings Kitchen sink.
Every family unit shall contain within its walls a kitchen
sink.
(Prior code § 78-37)
13-196-400
Residential buildings Heating facilities.
Every family unit shall have heating facilities which are
capable of safely and adequately heating all habitable
rooms, bathrooms and water closet compartments within its
walls to a temperature of at least 65 degrees Fahrenheit,
when the outside temperature is ten degrees below zero
Fahrenheit. Gas appliances designed primarily for cooking or
water heating purposes shall not be considered as heating
facilities within the meaning of this section. Portable
heating equipment employing flame and the use of gasoline as
a fuel does not meet the requirements of this section and is
prohibited. The owner may require that the occupant shall
provide the required heating facilities at the occupants
expense but such agreement or requirement does not relieve
the owner from responsibility for the presence of such
heating equipment in the family unit.
(Prior code § 78-38)
13-196-410
Residential buildings Heat to be furnished.
Every family unit or rooming unit to which heat is
furnished from a heating plant used in common for the
purpose of heating the various rooms of the dwelling shall
be supplied with heat from September 15th of each year to
June 1st of the succeeding year so that the occupants of a
family unit or rooming unit may secure, without such undue
restriction of ventilation as to interfere with proper
sanitary conditions, a minimum temperature of 68 degrees at
8:30 a.m. and thereafter until 10:30 p.m. and 66 degrees at
10:30 p.m. and thereafter until 8:30 a.m. averaged
throughout the family unit or rooming unit.
(Prior code § 78-39;
Amend Coun. J. 2-25-88, p. 10733; Amend Coun. J. 3-9-05, p.
43526)
13-196-420
Residential buildings Cold and hot water lines.
Every kitchen sink, lavatory and bathtub or shower required
shall be connected with hot and cold water lines. The hot
water lines shall be connected with water heating facilities
which are capable of heating water to such a temperature as
to permit water to be drawn at every required outlet at a
temperature of not less than 120 degrees Fahrenheit even
when the heating facilities required by this Code are not in
operation.
(Prior code § 78-40)
13-196-430
Residential buildings Hot water to be furnished.
Every family unit or rooming unit to which hot water is
furnished from water heating facilities used in common shall
be supplied with hot water throughout the year so that the
occupants may draw water at every hot water outlet between
the hours of 6:00 a.m. and 10:30 p.m. of a minimum
temperature of 120 degrees Fahrenheit.
(Prior code § 78-41)
13-196-440
Gas-fired appliances.
All gas-fired heating, cooking and other appliances and
gas-fired water heaters, shall conform to the requirements
in Sections 13-152-390* through 13-152-440* and 13-180-100*
and 13-180-230* of the building provisions of this Code
concerning installation, vents and flues.
(Prior code § 78-42)
13-196-450
Residential buildings Hall and stairway lighting.
Every public hall and stairway in every dwelling having
more than one family unit shall be adequately lighted at all
times, except that in a two-family dwelling an adequate
lighting system which may be turned on when needed by
conveniently located light switches shall be permitted
instead of a full-time lighting system.
(Prior code § 78-43)
13-196-460
Residential buildings Storage beneath stairways.
There shall be no closets or storage of any kind beneath
stairways in any dwelling containing two or more family
units or in any roominghouse unless the stair complies with
the fire resistive requirements of Sections 15-8-120 to
15-8-180 inclusive, or unless the stairs and storage space
are separated by noncombustible materials having a fire
rating of not less than one hour. No combustible or
flammable materials, fluids, or compounds shall be placed,
stored or kept in any place inside or outside of any
building where the ignition or burning of such materials,
fluids, or compounds would obstruct or render hazardous the
egress from any family unit or from the building.
(Prior code § 78-44)
13-196-470
Residential buildings Space, use and location
Applicability of provisions.
No person shall occupy or cause or permit the continued
occupancy of any family unit which does not comply with the
standards of occupancy set forth in Sections 13-196-480
through and including 13-196-520 of this chapter.
The provisions of Sections 13-196-480 through and including
13-196-520 shall not be applicable to single- family
dwellings occupied only by an owner and persons within the
family relationship.
(Prior code § 78-45)
13-196-480
Residential buildings Space requirements
Every family unit shall contain at least 125 square feet of
floor area for each of the first two occupants, and at least
100 square feet of each of the next two occupants, and at
least 75 square feet for each additional occupant. For the
purpose of this section, floor area is the area within the
perimeter of the space or building occupied by the family
unit, not including elevators, stairs, or other shaft
enclosures.
(Prior code § 78-46)
13-196-490
Residential buildings Space requirements Sleeping rooms.
In every family unit and every rooming unit, every room
occupied for sleeping purposes by one occupant shall contain
at least 70 square feet of floor area, or if of original
configuration need only comply with the regulations in
effect at the time of its construction. Every room occupied
for sleeping purposes by more than one occupant shall
contain at least 50 square feet of floor area for each
occupant 12 years of age and over and at least 35 square
feet of floor area for each occupant under 12 years of age.
For the purpose of this section a person under two years of
age shall not be counted as an occupant.
(Prior code § 78-47)
13-196-500
Residential buildings Access to water closets.
Every room used exclusively as a bedroom shall have access
to at least one water closet without passing through another
room used exclusively as a bedroom.
(Prior code § 78-47)
13-196-510
Residential buildings Ceiling heights.
At least one-half of the floor area of every habitable room
shall have a ceiling height of not less than seven feet; and
the floor area of that part of any room where the ceiling
height is less than five feet shall not be considered as
part of the floor area in computing the total floor area of
the room for the purpose of determining the maximum
permissible occupancy thereof. However, in any room, beams
or furred spaces constituting not more than 25 percent of
the ceiling area, may have a height of not less than six
feet.
(Prior code § 78-49)
13-196-520
Residential buildings Basement units.
A basement space used as a habitable room or family unit
shall comply with the following:
1. The floor depth below grade is not
limited if the floors and walls are impervious to leakage of
underground and surface runoff water and are protected
against dampness.
2. The required minimum window area is
located entirely above the finished elevation of the ground
adjoining the building wall in which the windows are
located.
(Prior code § 78-50)
13-196-530
Residential buildings Foundations, exterior walls and
roofs Maintenance.
The foundation, exterior walls, and exterior roof shall be
substantially watertight and protected against rodents, and
shall be kept in sound condition and repair:
(a) The foundation elements shall
adequately support the building at all points.
(b) Every exterior wall shall be free of
holes, breaks, loose or rotting boards or timbers, and any
other conditions which might admit rain, or dampness to the
interior portions of the walls or to the exterior spaces of
the dwelling.
(c) The roof shall be tight and have no
defects which admits rain and roof drainage shall be
adequate to prevent rain water from causing dampness in the
walls.
(d) The dwelling shall be in a
rat-stopped condition, in accordance with Sections 7-28-660
through 7-28-730 of this Code, and shall be adequately
protected against the entry of other rodents.
(e) All cornices, rustications, quoins,
moldings, belt courses, lintels, sills, oriel windows,
pediments and similar projections shall be kept in good
repair and free from cracks and defects which make them
hazardous and dangerous.
(Prior code § 78-51)
13-196-540
Residential buildings Floors, interior walls and ceilings
Maintenance.
Every floor, interior wall, and ceiling shall be kept in
sound condition and good repair and further,
(a) Every floor shall be free of holes
and wide cracks which might admit rodents or which
constitute a possible accident hazard.
(b) Every floor shall be free of loose,
warped, protruding, or rotting floor boards.
(c) Every interior wall and ceiling
shall be free of holes and large cracks.
(d) All interior walls, ceilings and
interior woodwork shall be free of flaking, peeling, chipped
or loose paint, plaster or structural material.
(e) Plaster, paint and other surface
materials shall be of such character as to be easily
cleanable, and are reasonably smooth, clean and tight.
(f) Every toiletroom and bathroom floor
surface shall be substantially impervious to water and be
capable of being maintained easily in a clean and sanitary
condition.
(Prior code § 78-52)
13-196-550
Residential buildings Windows, doors and hatchways
Maintenance.
Every window, exterior door, and basement hatchway shall be
substantially tight, and shall be kept in sound condition
and repair, and
(a) Every window shall be fully supplied
with window panes which are without open cracks or holes.
(b) Every window sash shall be in good
condition and fit reasonably tight within its frame.
(c) Every window, other than a fixed
window, shall be capable of being easily opened and shall be
held in position by window hardware.
(d) Every exterior door, door hinge, and
door hatch shall be in good condition.
(e) Every exterior door, when closed,
shall fit reasonably well within its frame.
(f) Every window, door, and frame shall
be constructed and maintained in such relation to the
adjacent wall construction as completely to exclude rain,
and substantially to exclude wind from entering the
dwelling.
(g) Every basement hatchway shall be so
constructed and maintained as to prevent the entrance of
rodents, rain, and surface drainage water into the dwelling.
(h) Every door available as an exit as
required by this chapter shall be capable of being opened
from the inside, easily and without the use of a key.
(Prior code § 78-53)
13-196-560
Residential buildings Screens.
Screens shall be supplied to the following extent:
(a) Every basement or cellar window
which is openable shall be supplied with a heavy wire screen
or hardware cloth of not less than four mesh per inch which
fits tightly and is securely fastened to the frame, or with
any other material affording equivalent protection against
the entry of rodents.
(b) From April 15th to November 15th of
each year, every door opening directly from any family unit
to the outdoors and every window, or other outside openings
used for ventilation purposes, shall be supplied with a
screen of not less than 16 mesh per inch and every screen
door shall have a self-closing device in good working
condition. Except for existing screens, which shall not be
removed without the written consent of the person entitled
to possession of the unit, no screens shall be required for
a family unit on a floor above the fourth floor, unless
required by the department of buildings and fire department
when unusual circumstances of insect prevalence exists.
(Prior code § 78-54;
Amend Coun. J. 9-13-89, p. 4604; Amend Coun. J. 6-27-90, p.
17617)
13-196-570
Residential buildings Stairways and porches Maintenance.
Every stairway, inside or outside of the dwelling and every
porch, shall be kept in safe condition and sound repair and:
(a) Every flight of stairs and every
porch floor shall be free of holes, grooves, and cracks,
which are large enough to constitute possible accidents
hazards.
(b) Every stairwell and every flight of
stairs, which is more than two risers high, shall have rails
not less than two and one-half feet high, measured
vertically from the nose of the tread to the top of the
rail; and every porch which is more than two risers high
shall have rails not less than three and one-half feet above
the floor of the porch.
(c) Every rail and balustrade is firmly
fastened and is maintained in good condition.
(d) No flight of stairs shall have
settled more than one inch out of its intended position or
have pulled away from supporting or adjacent structures.
(e) No flight of stairs shall have
rotting, loose or deteriorating supports.
(f) The riser height and the tread width
of each flight of stairs shall be uniform.
(g) Every stair tread shall be sound and
be securely fastened in a substantially level position.
(h) Every stair tread shall be strong
enough to bear a concentrated load of at least 400 pounds
without danger of breaking.
(i) Every porch shall have a sound
floor.
(j) No porch shall have rotting, loose
or deteriorating supports.
(Prior code § 78-55)
13-196-580
Residential buildings Basements and cellars Maintenance.
Every basement and every cellar shall be maintained in a
safe and sanitary condition, and:
(a) Water shall not be permitted to
accumulate or stand on the floor.
(b) All sewer connections shall be
properly trapped.
(c) All cellar and slab drains shall be
covered with grating.
(d) Junk, rubbish, and waste shall not
be permitted to accumulate to such an extent as to create
fire hazards or to endanger health or safety.
(Prior code § 78-56)
13-196-590
Residential buildings Facilities, equipment, chimneys
Maintenance.
Every supply facility, piece of equipment or utility, and
every chimney and chimney flue, shall be installed and
maintained in a safe and sound working condition.
(Prior code § 78-57)
13-196-600
Residential buildings Lot grading and drainage.
Every yard, court, vent passageway, and other portions of
the lot on which the dwelling stands shall be graded and
drained so as to prevent the accumulation of stagnant water
on any such surface.
(Prior code § 78-58)
13-196-610
Residential buildings Responsibilities of owners and
occupants General.
In addition to other applicable provisions of this Code,
owners and occupants of residential buildings shall comply
with the respective responsibilities imposed upon them by
Sections 13-196-620 through and including 13-196-640 of this
chapter.
(Prior code § 78-59)
13-196-620
Residential buildings Responsibilities of occupants.
Every occupant of a family unit must:
(a) Keep that part of the family unit
which he occupies and controls in a clean, sanitary and safe
condition;
(b) Keep all plumbing and other fixtures
required by this chapter, whether or not supplied by the
landlord, in a clean and sanitary condition, and if supplied
by the landlord, must use reasonable care in the proper use
and operation thereof;
(c) If a single-family dwelling unit,
exterminate any insects, rodents or other pests therein or
on the premises and, if a family unit in a dwelling
containing more than one family, exterminate such insects,
pests, and rodents whenever his family unit is the only one
in the dwelling infested, except as provided in Section
13-196-630 (c);
(d) Dispose of all garbage and other
refuse only in the containers required by Section 7-28-220
of the code and must place such refuse in the containers in
a clean and sanitary manner;
(e) Hang and remove all screens required
for the family unit by this chapter unless the owner has
agreed to supply such service;
(f) Not place on the premises any
material which may cause a fire hazard or otherwise
endangers the health or safety of any occupant of such
dwelling, nor place in storage on the premises any
furniture, equipment, or material which harbors insects,
rodents, or other pests;
(g) Not permit any family unit let to
him to be occupied so that any occupancy resulting therefrom
violates any of the provisions of this chapter;
(h) Provide heating facilities for that
part of the family unit he occupies unless such facilities
are provided by the owner. Gas appliances designed to be
used primarily for cooking or water heating purposes shall
not be considered as heating facilities within the meaning
of this section.
(Prior code § 78-60)
13-196-630
Residential buildings Responsibilities of owner or
operator.
Every owner or operator must:
(a) Comply with the requirements imposed
on him by this chapter;
(b) Maintain in a clean, sanitary and
safe condition the shared or public areas of the dwelling or
premises, and maintain and repair any equipment of a type
specified in this Code which he supplies or is required to
supply;
(c) Exterminate any insects, rodents or
other pests in any family unit, if infestation is caused by
the failure of the owner or operator to maintain the
dwelling in a ratproof or reasonable insect-proof condition,
and he must exterminate such pests in any family unit in the
dwelling, regardless of the cause of infestation, if
infestation exists in two or more of the family units in the
dwelling or in the shared or public parts of any dwelling
containing two or more family units; and
(d) Supply and maintain the facilities
for refuse disposal which are required of him by Section
7-28-220.
(Prior code § 78-61)
13-196-640
Residential buildings Liability to city.
An owner remains liable to the city for violation of duties
imposed upon him by this chapter even though:
(a) An obligation is also imposed on the
occupant by this chapter; or
(b) The owner has by agreement imposed
on the occupant the duty of furnishing required equipment or
of complying with this chapter.
(Prior code § 78-62)
13-196-641
Application of certain sections.
The provisions of Sections 13-196-530 through 13-196-640,
inclusive, shall apply to all existing buildings, regardless
of use or occupancy.
(Added Coun. J.
7-25-01, p. 64897, § 12)
13-196-650
Pre-ordinance conversion to existing buildings
Applicability.
A pre-ordinance (built before July 8, 1957) residential
building or building of mixed residential occupancy not
complying with the requirements in force and applicable to
the building at the time of its conversion may, if permitted
by the Zoning Ordinance, be altered so as to legalize the
present number of dwelling units provided such building
complies with all the provisions of Chapter 13-196. For
conversions which have added only one additional dwelling
unit over the original number permitted, the provisions of
Section 13-196-740 shall apply.
(Prior code § 78-63)
13-196-660
Conversion of pre-ordinance buildings Height limits.
The said pre-ordinance building shall be not more than four
stories in height if of ordinary construction, or two
stories in height if of frame construction.
(Prior code § 78-64)
13-196-670
Stairwells.
New and existing stairwells are to be separated from all
other parts of the building with partitions providing a fire
resistance rating of not less than one hour. Stairwells,
doors, and frames are to comply with Section 15-8-180. Stair
soffits shall be protected with wood lath and plaster, or
one hour construction.
(Prior code § 78-65)
13-196-680
Corridors.
Partitions enclosing public corridors must have a fire
resistance rating of not less than one hour, and corridor
doors and frames are to comply with Section 13-64-020 (b).
(Prior code § 78-66)
13-196-690
Dwelling separations.
Partitions separating dwelling units or between dwelling
units and other occupancies, including heating plants must
be of one-hour-fire-rated construction.
(Prior code § 78-67)
13-196-700
Partitions.
All partitions are to be of original construction or of a
half-hour-fire-rated construction. Existing partitions may
be altered or replaced with material allowed in the original
structure.
(Prior code § 78-68)
13-196-710
Basement ceiling construction.
Floor construction over the basement shall be a minimum of
a half hour construction when the building contains three
dwelling units or more.
(Prior code § 78-69)
13-196-720
Heating plants.
Furnaces or other heating plants shall be enclosed with a
minimum of a half hour construction when the building
contains three dwelling units or more.
(Prior code § 78-70)
13-196-730
Light and ventilation.
Light and ventilation requirements are to comply with code
provisions in effect at the time the building was originally
constructed or they may comply with present requirements for
new construction except as follows:
(a) A kitchen with a floor of less than
70 square feet may be without either mechanical or natural
ventilation if there is an opening of not less than 32
square feet between the kitchen and another room in the same
family unit and if the room into which the kitchen opens
meets the ventilation requirements of this Code.
(b) Every toilet room and bathroom shall
have adequate ventilation which may be either an openable
window with an operable area of five percent of the floor
area, mechanical ventilation complying with the requirements
of Chapter 13-176*, or a gravity vent flue constructed with
incombustible leading to the roof of the building, or a
combination of any of these. The gravity vent shall be
computed at an aggregate clear area of not less than five
percent of the floor area of the room, with a minimum area
of at least 120 square inches. Gravity vents shall be
provided with a weather cap, directional vane, or rotary
type ventilation on roof.
(Prior code § 78-71)
13-196-740 One
additional dwelling unit over original allowed Conditions.
A pre-ordinance (built before July 8, 1957) residential
building or building of mixed residential occupancy, not
complying with the requirements in force and applicable to
the building at the time of its conversion, may be altered
so as to legalize one dwelling unit, in addition to the
number of dwelling units originally authorized, providing
that said unit was determined by the office of the zoning
administrator or the zoning board of appeals to have existed
prior to July 8, 1957, and provided such building complies
with the other provisions of this chapter. Such conversion
need not comply with the requirements of the following
specific provisions of this chapter:
(a) Section 13-196-660 (height limits);
however, in frame buildings, four or more levels of living
space shall be prohibited and in buildings of ordinary
construction, with or without attic living space, five or
more levels shall be prohibited;
(b) Section 13-196-050; however, all
dwelling units must comply with the exit provisions of
Chapter 13-160 except basement dwelling units may have a
second exit through a room containing a heating plant;
(c) Section 13-196-670 (stairwell
enclosures);
(d) Section 13-196-680 (corridor
enclosures);
(e) Section 13-196-690 (dwelling
separations);
(f) Section 13-196-710 (basement ceiling
construction); however, if the basement contains a dwelling
unit the entire basement ceiling construction is to be wood
lath and plaster of half hour construction;
(h) Section 13-196-720 (heating plants);
however, basement apartments are to be separated from
heating plants with partitions of one hour construction.
(Prior code § 78-72;
Amend Coun. J. 6-14-95, p. 2841)
13-196-750
Heat required.
It shall be the duty of every person owning or controlling
the heating plant which furnishes heat to any factory or
workshop, to maintain a temperature within such factory or
workshop of not less than 68 degrees Fahrenheit without such
undue restriction of ventilation as to interfere with proper
sanitary conditions therein; provided, however, that this
requirement shall not apply to any factory or workshop where
the business conducted therein is of such a nature that a
higher or lower temperature than 68 degrees Fahrenheit is
necessary or expedient for the work, or manufacturing
processes of such business; and provided, further, that in
all such cases, when such higher or lower temperature is
necessary or expedient, the moisture content of the air
shall be increased where the temperature is maintained below
68 degrees Fahrenheit or decreased where the temperature is
maintained above 68 degrees Fahrenheit in the proper amount
to maintain a wet bulb temperature between 54 degrees and 58
degrees Fahrenheit, and in the case of special manufacturing
processes where it is necessary or expedient to maintain a
wet bulb temperature below or above the extremes herein set
forth, the commissioner of buildings shall prescribe and
enforce such reasonable precautions and safeguards as will
meet the requirements of such special manufacturing
processes without endangering the health of the occupants of
such factory or workshops. The manner of determining the
temperature in all cases where the temperature to be
maintained is 68 degrees Fahrenheit shall be the same as in
Section 5-4-060, and in all other cases shall be in such
practical manner as the commissioner of buildings may
determine.
It shall be the duty of any person owning or controlling
the heating plant which furnishes heat to any office, store,
or other place of employment to maintain a temperature
therein of not less than 68 degrees Fahrenheit without such
undue restriction of ventilation as to interfere with proper
sanitary conditions therein, between the hours of 8:00 A.M.
and 6:00 P.M., from October 1st of each year to June 1st of
the succeeding year, Sundays and full legal holidays
excepted.
The provisions of this section shall apply to every
existing building or portion thereof containing a factory or
workshop, office, store or other place of employment, as the
case may be.
(Prior code § 96-27;
Amend Coun. J. 3-31-04, p. 20916, § 2.6)
13-196-760
Endangering health of employees.
Every owner or person in charge of any existing factory
shall cause the temperature of every part thereof in which
any person may work to be so maintained, and such
accommodations and safeguards to be provided as not to
cause, by reason of the want thereof or by reason of the
condition of any such factory or its appurtenances,
unnecessary danger or detriment to the health of any person
employed therein.
(Prior code § 96-28;
Amend Coun. J. 3-31-04, p. 20916, § 2.7)
|